Troubleshooting the Burner
Cub 200/300
52
ghi_tx001207gb.fm
Continued from the previous page.
4. Turn the machine on. If the machine is in a fault condition, press the RESET
(c)
button on the control panel.
5. Measure the voltage at the connector
(d)
. To do so, you must wait through the
10-second prepurge cycle.
Note: The voltage will only be present for approximately 1 second after the
prepurge cycle ends. It may take more than one attempt to measure the voltage.
Is 108–132 VAC measured?
6. Turn the machine off and disconnect the power source.
This procedure continues on the next page.
Yes ____
No ____
Continue.
The wiring to the fuel solenoid has failed. Shut down the machine
and repair this wiring.