EN
VTS reserves the right to implement changes without prior notice
User’s Manual
29
Note!
The universal relay REL3 or REL6 must be set to
UniReg or NOTUniReg – to let the resulting signal out of the
controller.
3.6. ALARM MENU
ALARM MENU
Alarm menu can be accessed via dedicated button on the
HMI Advanced
NAME
– description of the feature or function that was in
alarm state, e.g. Modbus comm
STATUS
– current condition of the alarm, OK – inactive,
ALARM – active
TYPE
– de
fi
nes the group of alarm events – Normal – these
are mostly non-remanent alarms of lower priority; Critical
– these are mostly remanent alarms of higher priority, that
could even stop and block the unit from further operating.
DATE / TIME
– time stamp when the alarm occured
Note! To acknowledge the alarm currently displayed on the
HMI, press PRG button.
Another way of cancelling the alarms is turning the power
Off and On again. At startup all alarms are cleared, except
of those, that are stiil activated by input signals.
Note!
Alarms can be remanent – they are locked until fixed
and acknowledged, e.g. the fire alarm. Or can be non-
remanent – they unlock, when the alarm signal is fixed and
don’t need to be acknowledged to go to the history records,
e.g. the filter alarm.
HMI ADVANCED
ALARMS
NAME
Fire alarm
STATUS
ALARM
TYPE
Critical
DATE
05.07.11
TIME
10:11
ALARMING IN HMI BASIC
Alarm in HMI Basic are displayed instead of time indication
in a form of a letter and number, like AL15. The number is
given to identify what is the source of alarm.
Note! HMI Basic cannot acknowledge alarms. All non-
remanent events will disappear automatically. All remanent
events need to be reset by means of HMI Advanced, or by
switching off / on the power supply.
List of alarm codes:
AL01
. Fire alarm
AL02
. HW thermostat
AL03
. HW back-water
AL04
. Pre-HW thermost
AL05
. Pre-HW back-wtr
AL06
. HE overheat
AL07
. Supply sensor
AL08
. Exhaust sensor
AL09
. Room sensor
HMI BASIC