User’s Manual
27
Freq. high limit
– upper boundary of the frequency
Range: 35..65Hz
Default: 55Hz
3.5.20. SETTINGS
FANS FIRE MODE
Settings for the fan behavior when there’s a
fi
re alarm
signal
Sup
fi
re setp - 0..100%
- setpoint for fan rate in
fi
re
conditions, 0% = fan stopped
Exh
fi
re setp - 0..100%
- setpoint for fan rate in
fi
re
conditions, 0% = fan stopped
Fire temp limit
- setpoint for the supply and exhaust duct
temperature that triggers the alarm signal
Range: 60..99
Default: 99
HMI ADVANCED
FANS FIRE MODE
Sup
fi
re setp
Exh
fi
re setp
Fire temp limit
3.5.21. SETTINGS
UNIVERSAL REGULATOR
The universal controller allows the use to implement some
speci
fi
c functionalities, that are not supported by original
Ventus applications.
The structure of the universal controller contains of two
main blocks:
comparator
– to check the relation between two signals
(can be selected from the program variables or from
universal analog input)
HMI ADVANCED
logic block
– the output from the comparator can be
processed by a logic function with another binary value
(from the program or from the binary input)
the binary output
– can do simple on/off control to
external actuators via universal relay 1 or 2
44 < 50 AND Off = Off – current status line, shows all
Input values, all functions and resulting output
Signal source
– select signal source to be compared with
a reference in comparator block
AI7
– user con
fi
gurable analog input
SupplyTmp
– supply temperature [°C]
RoomTmp
– room temperature [°C]
ExhustTmp
– exhaust temperature [°C]
RecovrTmp
– temperature after the heat recovery unit [°C]
ExternTmp
– external temperature [°C]
HeatgRate
– heating rate [%]
CoolgRate
– cooling rate [%]
RecovRate
– heat recovery rate [%]
SupFnRate
– supply fan rate [%]
ExhFanRate
– exhaust fan rate [%]
Compare function
– type of compare action
Less
– check if the source signal is less than the reference
Greater
UNIV REGULATOR
44 < 50 AND Off = Off
Signal src
AI7
Compare func
Less
Setpoint src
AI7
Const:
Hyst:
Logic block
AND
Logic source
DI6