3.4.13. PARAMETERS
SUPPLY PRESSURE TRANSDUCER
Pressure
- actual value of air pressure
Air
fl
ow
-
calculated air volum
fl
ow
Set Point
-
actual seting value of air volum
fl
ow
HMI ADVANCED
SUPPLY AIR FLOW
Pressure
800 Pa
Air
fl
ow
11240 m3/h
SetPoint
12003 m3/h
3.4.14. PARAMETERS
EXHAUST PRESSURE TRANSDUCER
Pressure
- actual value of air pressure
Air
fl
ow
- calculated air volum
fl
ow
Set Point
- actual seting value of air volum
fl
ow
HMI ADVANCED
EXHAUST AIR FLOW
Pressure
800 Pa
Air
fl
ow
11240 m3/h
SetPoint
12003 m3/h
3.4.15. PARAMETERS
REDUNDAN
Working time –
information on hours worked fans
1st set – a
fi
rst set of fans
2nd set – a second set of fans
Active set of fans -
the currently running a set of fans
1st set – a
fi
rst set of fans
2nd set – a second set of fans
• \/
□
- stop/start
HMI ADVANCED
REDUNDANT
Working time
1st set
123
h
2nd set
200
h
Active fans
1st set
□
2nd set
□
3.5. SETTINGS
TIMERS
On-delay
- setting for startup delay, from start command to
the actual startup of the unit
Idle
- setting for startup procedure, in idle state the fans run
at lowest speed, dampers are opening and all the heating/
cooling/recovery and protective regulators enter normal
operation mode
Off-delay
- setting for delayed stopping of the fans, can
be used to cool down electric heater or to run down the DX
cooling system
HMI ADVANCED
TIMERS
Sup
Exh
On-delay
20s
10s
Idle
20s
30s
Off-delay
10s
10s
3.5.1. SETTINGS
STANDBY
Enable
– activate the standby functionality
No
– function disabled
Yes
– function enabled
Start Htg
– temperature at which the heating is activated
Setpoint Htg
– temperature at which the heating is turned
off
Start Clg
– temperature at which the cooling is activated
Setpoint Clg
– temperature at which the cooling is turned
off
Min work time
– min. running time in standby mode
Min delay
– min. resting time after working in standby
mode
HMI ADVANCED
STANDBY
Enable
Yes
Start Htg
16,0°C
Setpoing Htg
22,0°C
Start Clg
27,0°C
Setpoing Clg
18,0°C
Min work time
60s
Min delay
600s