User’s Manual
19
3.5.2. SETTINGS
NIGHT COOLING
Enable
– activate the night cooling functionality
No
– function disabled
Yes
– function enabled
Min ext temp
– night cooling function is disabled below
that limit of external temperature
Min work time
– min. working time for the nigh cooling
Min delay
- min. time when the function cannot be enabled
again
HMI ADVANCED
NIGHT COOLING
Enable
Yes
Min ext temp
18,0°C
Min work time
60s
Min delay
60s
3.5.3. SETTINGS
NIGHT TEST
Night cooling and Standby functions rely on room
temperature. If there’s no temperature measurement in
the room, the exhaust duct sensor is taken into account
and gives the readout. This requires turning on the fans
to refresh the air and have appropriate room temperature
value on that sensor.
Enable
– activate the night test functionality
No
– function disabled
Yes
– function enabled
Test hour
– setting the time, when the night test function
will be triggered. The night test operates in a daily manner.
Test duration
– speci
fi
es how long the night test will be
executed
Note!
If during the Night Test operation, conditions for
Night Cooling or Standby will be detected, the unit will
automatically switch to another relevant mode.
Note!
Night Test functionality will not be triggered if external
temperature is lower than Min Ext Temp for Night Cooling.
HMI ADVANCED
NIGHT TEST
Enable
Yes
Test hour
05:15
Test duration
60s
3.5.4. SETTINGS
FAST HEATING
Enable
– activate the fast heating functionality
No
– function disabled
Yes
– function enabled
Temp deviation
– the fast heating algorithm will be
executed until the main temperature is lower than the
setpoint by the value of Temp deviation
HMI ADVANCED
FAST HEATING
Enable
Yes
Temp deviation
5,0°C
3.5.5. SETTINGS
TEMPERATURES
Setpoint Hi
– setting for upper boundary of temperature
setpoint
Range: 20..40
Default: 26
Setpoint Lo
– setting for lower boundary of temperature
setpoint
Range: 0..20
Default: 16
Deadzone LOW
– settings for the allowed non-sensitive
range in Low mode
Range: 0..10
Default: 4.0
HMI ADVANCED
TEMPERATURES
Setpoint Hi
26,0°C
Setpoint Lo
16,0°C
Deadzone LOW
4,0°C
Deadzone ECO
2,0°C
Deadzone COMF
1,0°C
Min Clg temp
16,0°C