EN
VTS reserves the right to implement changes without prior notice
User’s Manual
17
3.4.8. PARAMETERS
PRE-HEATING
Temperature
– current readout from sensor dedicated for
pre-heating coil
Setpoint
– current setpoint for the regulator, read only
Heating rate
– indicates current heating capacity
0% – no heating, 100% – full heating
Pump status
– indicates current state of the circulation
pump
Alarm status
– indicate the state of frost protection input
Note!
The pre-heating coil works out of the standard
cooling/heating sequence. It is intended just to keep the
constant temperature in specified place, e.g. to heat up
outside air before entering the heat recovery unit.
HMI ADVANCED
PRE-HEATING
Temperature
-10,0°C
Setpoint
-11,0°C
Heating rate
40%
Pump status
On
Alarm status
OK
Back-water
20,0°C
3.4.9. PARAMETERS
SUP MOTORS
3.4.10. PARAMETERS
EXH MOTORS
Freq
- actual output frequency
Current
- actual current consumption
Status
- combined information for communication problems
and for motor alarms
OK
- no malfunctions
Comm
- communication to the frequency converter not
stable or lost
Alarm
- communication OK, but frequency converter
reported an error, e.g. overload
Note!
Ventus AHU can have up to 4 frequency converters
in one fan set (MultiFan configuration). All FCs in the
fan set have common settings for frequency, ramp-up,
ramp-down and the main limits – as they must work
synchronously.
Note!
FC details visible only if frequency converters were
enabled during unit configuration
HMI ADVANCED
SUP MOTORS
Freq
Current
Status
1: 40,0Hz
4,1A
OK
2: 40,0Hz
4,3A
OK
3: 40,0Hz
4,2A
OK
4: 40,0Hz
4,2A
OK
3.4.11. PARAMETERS
SUPPLY PRESSURE TRANSDUCER
Pressure -
actual value of air pressure
Set Point -
actual setting value of air pressure
HMI ADVANCED
SUPPLY AIR PRESSURE
Pressure
800
Pa
SetPoint
799
Pa
3.4.12. PARAMETERS
EXHAUST PRESSURE TRANSDUCER
Pressure -
actual value of air pressure
Set Point -
actual setting value of air pressure
HMI ADVANCED
EXHAUST AIR PRESSURE
Pressure
800
Pa
SetPoint
800
Pa