ECU converter PBS Version: 1.3
Page 8/43
2.1.2.3
Alarms / Parameterization
From the ECU data display, the parameter display can be accessed by pressing the
Down button.
With the
Up button the parameter display will left (..to ECU data display).
Within the parameter display you can scroll with the
Right button - or -
Left button
between the parameter groups "Alarm", "Alarmcode", "F-Flow/Pump", "Fueltank Size",
"ECU-EX-Name" and "Taxi Tank".
When the desired parameter group is selected, the parameter can be changed by using
Down and
Up button.
Value changes are made with the
Right button – or-
L
eft button.
Example of parameter selection and parameterization:
Down button
Right button
Down button
Right button (multiple times)
Up button
Up button
Parameter-
group
Parameter
Value range
Step size
Set- Value
(Default)
Alarm
F-RES
100
. . . 2500 ml
10 ml
800 ml
BATT
5.0
. . . 12.0 V
0.1 V
5.0 V
EGT
400
. . . 995 °C
5 °C
700 °C
RPM
20.000 . . . 99.900 rpm
100 rpm
OFF
Alarmcode
FUEL
A, B, C, . . . , X, Y, Z
C
BATT
U
EGT
T
RPM
L
F-Flow /
Pump
@ 1,5 V
10
. . . 600 ml/min
1 ml/min
112 ml/min
@ 3,0 V
10
. . . 2000 ml/min
1 ml/min
272 ml/min
Fueltank
Size
200
. . . 20.000 ml
100 ml
3.000 ml
Jeti-Sensor
EX Name
VSECU, L-ECU, R-ECU, 1LECU, 2RECU
VSECU
Taxi Tank
OFF, ON
OFF
Taxi Tank