10
Functions
Each appliance, equipped with a 5-speed EC motor, has two modes of operation (trickle mode at minimum speed
and boost mode at maximum speed).
The operating speed in trickle mode, which is set during installation according to requirements of the destination
room, corresponds to the following air flow rates: 36/ 41/ 51/ 56 m
3
/h (10/ 11,4/ 14,2/ 15,6 L/s).
The possible configurations (four for trickle mode operation) divided by air flow are shown in the following table
(for the wiring diagrams see figures 26 ÷ 29 on page 23 ÷ 24):
ENGLISH
The appliance is provided with basic functions or with timer and HCS, as specified below:
Basic model (dMEV)
There are no user-settable parameters:
• Programming button is disabled;
When the fan is activated, the LED blinks for 10 minutes to indicate the set speed.
•
Speed 1:
led blinks once (LED ON 0,2s / LED OFF 0,2s) at 2 seconds intervals
•
Speed 2:
led blinks twice (LED ON 0,2s / LED OFF 0,2s) at 2 seconds intervals
•
Speed 3:
led blinks 3 times (LED ON 0,2s / LED OFF 0,2s) at 2 seconds intervals
•
Speed 4:
led blinks 4 times (LED ON 0,2s / LED OFF 0,2s) at 2 seconds intervals
•
Speed 5:
led blinks 5 times (LED ON 0,2s / LED OFF 0,2s) at 2 seconds intervals
Model Timer + HCS (dMEV T-HCS)
• These models are equipped with an electronic circuit board with relative humidity sensor and timer.
• Programming button is enabled
TIMER FUNCTION
The function performed by the timer is as follows:
• The fan operates at the minimum speed (TRICKLE mode) set at installation.
• It is timed only the maximum speed (BOOST mode) as follows:
• Only the maximum speed (BOOST mode) starting time is programmable, as follows:
• Fan switches on at 68 m
3
/h (18,9 L/s). in BOOST mode, following a delay of 0s, 45s, 90s or 120s selectable
with the programming button.
• Return of the fan to TRICKLE mode, following a delay of 6min, 10min, 15min or 21min selectable with the
programming button.
Mode
Speed
Air flow (m
3
/h)
Air flow (L/s)
trickle
1
36
10
trickle
2
41
11,4
trickle
3
51
14,2
trickle
4
56
15,6
Mode
Speed
Air flow (m
3
/h)
Air flow (L/s)
boost
5
68
18,9
The boost mode, present on all models, is operated by a switch and guarantees a flow rate of 68 m
3
/h (18,9 L/s).
Summary of Contents for VORT QUADRO dMEV
Page 1: ...VORT QUADRO dMEV COD 5 571 084 597 04 09 2020 Libretto istruzioni Instruction booklet...
Page 13: ...13 FIGURE FIGURES 1 1 A...
Page 14: ...14 3 4 VORT QUADRO dMEV I 2...
Page 15: ...15 5 mt 2 3 6...
Page 16: ...16 mt 2 3 5 1 6 1...
Page 17: ...17 7 1 8 1...
Page 18: ...18 7 9 7 10...
Page 19: ...19 11 12...
Page 20: ...20 VORT QUADRO dMEV 7 13 7 14...
Page 21: ...21 7 15 16 17...
Page 22: ...22 18 20 19...
Page 23: ...23 21 22...
Page 24: ...24 23 24...
Page 27: ...27 30 31 32...
Page 33: ...33 Figure accessori Figures accessories 1 A A A A QE MH...
Page 34: ...34 2 A B B C 3...
Page 35: ...35 4 A 5...
Page 36: ...36 QE UMB 6 A A C 7 A B B...
Page 37: ...37 8 A A B B 9 B B A...
Page 38: ...38 10 A 11 A B C 170 280 mm 95 205 mm 65 125 mm...
Page 40: ...40 Fissare la griglia con le viti Tighten the screws on the grid 14 15...
Page 41: ...41 Inserire il filtro Insert the filter 16 17...
Page 42: ...42 QE CFR 18 19...
Page 43: ......
Page 45: ......