ENGLISH
16
Description
Terminals
Connection
ADP (bridge if not used)
1-2
Connect to the terminals of a firefighter remote shutdown NF contact
DAD (bridge if not used)
3-4
Connect to the DAD fault contact
THA / THS
(bridge if not used)
5-6
Connect to the NF contact of the THA (PREMIUM BC)
Connect to the NF contact of the THS (PREMIUM BE)
ED-TOUCH
7-8 + A*-B* (port2)
Connect to the touch screen remote control
MF LS
9-10
Connect to the external NO voltage-free Low Speed Forced Run contact
MF HS
11-12
Connect to the external NO voltage-free High Speed Forced Run contact
ARR EST
13-14
Connect to the external NO voltage-free External Forced Shutdown contact
BC
15-16-17
BC
: Connect to the 3-way valve of the hot water coil (see section IV.12)
BE
18 + DO3**
BE
: Connect to the static contactor of the electric heater battery (see section IV.14)
Heating pump
(PREMIUM BC)
18 + DO3**
Connect to the M/A of the hot water pump (Caution: max. 24 V 2 A to be connected
via relay) (see section IV.12)
Cooling pump
(PREMIUM BC)
19 + DO4**
Connect to the M/A of the cold water pump (Caution: max. 24 V 2 A to be
connected via relay)** (see section IV.12)
AL
20 + DO5**
24 V output available in the event of system malfunction (Caution: max. 24 V 2 A to
be connected via relay)
NC (Night cooling)
(LOBBY®)
20 + DO7**
24 V output available if the system is configured with the LOBBY
®
EC option for
opening the terminal dampers during Night Cooling operation. (Caution: max. 24 V
2 A to be connected via relay)
TRPS
23 / Agnd* + UI1*
Connect to the supply pressure sender (see section IV.8)
DEPS
24 + UI1*
Connect to terminals 1 and 3 of the supply
DEP
(see section IV.7)
TRPR
25 / Agnd* + UI2*
Connect to the recovery pressure sender (see section IV.8)
DEPR
26 + UI2*
Connect to terminals 1 and 3 of the return
DEP
(see section IV.87)
CO2
27 / Agnd* UI3*
Connect to the CO2 sensor (see section IV.10)
BF
28-29-30
BF
: Connect to the 3-way valve of the hot water coil (see section IV.12)
DEP FS
DEP FR
31-32
33-34
Connect to terminals 1 and 3 of the
DEP
supply filter (see section IV.6)
Connect to terminals 1 and 3 of the
DEP
return filter (see section IV.6)
RMS
35 + DO1**
Connect to terminals 1 and 2 of the motorised supply damper
RMR
36 + DO2**
Connect to terminals 1 and 2 of the motorised recovery damper
WHEEL
37-38
21-22
Connect to the 0-10 V input of the wheel (see section IV.5)
Connect to the wheel malfunction return terminals (see section IV.5)
0-10V S
39-40
Connect to the fan or to the supply variator (see sections VIII.2 to 5)
0-10V R
41-42
Connect to the fan or the recovery variator (see sections VIII.2 to 5)
* Connect directly to the CORRIGO controller
** Connect directly to the CORRIGO controller and at a maximum 8A to the DO group
Summary of Contents for VORT NRG 1500 ECR
Page 40: ...ENGLISH 40 VIII APPENDICES VIII 1 Control diagram ROUE WHEEL FUSE CLAMP...
Page 50: ...ENGLISH 50 IX NOTES...
Page 83: ...FRAN AIS 83 VIII ANNEXES VIII 1 Sch ma de commande...
Page 93: ...FRAN AIS 93 IX NOTES...
Page 126: ...DEUTSCH 126 VIII ANLAGEN VIII 1 Schaltplan der Steuerung ROUE RAD MORSETTO FUSIBILE...
Page 136: ...DEUTSCH 136 IX ACHTUNG...