ENGLISH
47
Function
Description
Exo
type
Modbus
address
Bacnet
address
Default
value
System status
Modbus:
0= stop
1= start
2= low speed start
3= maximum speed start
4= normal speed start
5= In operation
8= CO2 operation
9= Night cooling
11= In shutdown
BACNET:
1= stop
2= start
3= low speed start
4= maximum speed start
5= normal speed start
6= In operation
9= CO2 operation
10= Night cooling
12= In shutdown
X
3
MSV,40003
External temperature
R
1
AV,40001
Operating time of the blower
fan
R
4
AV,40004
Operating time of the recovery
fan
R
5
AV,40005
Supply temperature
R
7
AV,40007
Extraction temperature
R
9
AV,40009
Fresh air pressure
R
13
AV,40013
Recovery air pressure
LOBBY
®
R
14
AV,40014
Fresh air flow rate
LOBBY
®
R
15
AV,40015
Recovery air flow rate
MAC2
®
/QUATTRO
®
R
16
AV,40016
CO2
MAC2
®
/QUATTRO
®
R
17
AV,40017
Humidity
DIVA
®
R
23
AV,40023
Analogue output
0-10 V heating (WATER COIL)
R
54
Analogue output
0-10 V Heat exchanger
R
55
Analogue output
0-10 V Heat exchanger
R
56
Analogue output
0-10 V Supply
R
57
Analogue output
0-10V Recovery
R
58
VIII.7. MODBUS and BACNET table
INPUT REGISTER
Summary of Contents for VORT NRG 1500 ECR
Page 40: ...ENGLISH 40 VIII APPENDICES VIII 1 Control diagram ROUE WHEEL FUSE CLAMP...
Page 50: ...ENGLISH 50 IX NOTES...
Page 83: ...FRAN AIS 83 VIII ANNEXES VIII 1 Sch ma de commande...
Page 93: ...FRAN AIS 93 IX NOTES...
Page 126: ...DEUTSCH 126 VIII ANLAGEN VIII 1 Schaltplan der Steuerung ROUE RAD MORSETTO FUSIBILE...
Page 136: ...DEUTSCH 136 IX ACHTUNG...