 OPERATING INSTRUCTIONS

VC64 TWO-PIN VOLTAGE TESTER

ITEM NO. 1313886

INTENDED USE

The two-pole voltage tester can be used to measure and display DC and AC voltages in an electrical 

low-voltage circuit. The product also has an acoustic and visual circuit indicator as well as a resistance 

measurement and an RCD test function. Power is supplied by two batteries of type  

AAA/Micro included in the delivery.
The voltage tester complies with the standard for two-pole voltage testers of 12 - 690 V, CAT III 1000 V, 

CAT IV 600 V according to EN 61243-3:2014/EN 60529 as well as protection class IP64 (dust and spray 

water). The product is suitable for use in dry or damp conditions. Use during rain or other precipitation is 

not permitted. The voltage tester is designed for use by electrically skilled persons using personal protec-

tive equipment.
The measuring instrument must not be operated when the battery compartment is open.
Measuring under adverse ambient conditions such as dust and flammable gases, vapours or solvents is 

not permitted.
Always observe the safety instructions and all other information included in these operating instructions.
This product complies with the applicable national and European requirements. All names of companies 

and products are the trademarks of the respective owners. All rights reserved.

PACKAGE CONTENTS

•  Voltage tester
•  2x batteries of type Micro/AAA
•  2x protective plastic covers 
•  2x 4 mm adapter to open probe tips
•  Operating instructions

EXPLANATION OF SYMBOLS

   The lightening flash symbol in a triangle warns against  the risk of an electric shock or interfer-

ence with the electrical safety of the device.

   An exclamation mark inside a triangle refers to important. notes in the operating instructions.

 The arrow symbol indicates special information and advice on operating the device.

SAFETY INSTRUCTIONS

   The warranty will expire in case of any damage caused by the failure to follow these 

operating instructions! We assume no liability for any resulting consequential damage!

 

 We assume no liability for any damage to property or personal injuries caused by 

improper use or non-compliance with the safety instructions! In such cases, the warranty 

will be null and void.

 

•   The unauthorised conversion and/or modification of the product is not permitted for safety and 

approval reasons. Do not disassemble the product.

 

•   This product is not a toy. Therefore, be especially careful when children are around. 

 

  Use the product where it is out of the reach of children. 

 

•   Never use the product immediately after it has been taken from a cold room to a warm one. 

The condensation that forms can ruin the product under certain circumstances.

 

•  Avoid the following adverse conditions at the location of installation and during transport:

 

  -  Extreme cold or heat, direct sunlight

 

  -  Dust or flammable gases, fumes or solvents

 

  -  Strong impacts, blows

 

•   Do not leave packaging material carelessly lying around, since it could become a dangerous 

plaything for children.

 

•   Handle the product with care, it can be damaged by impacts, blows, or accidental falls, even 

from a low height.

 

•   Never touch the measuring tips or a measuring point during the measuring process. There is 

a risk of electric shock.

 

•   Never touch areas outside of the marked handling area during a measurement.

 

•   Do not use in the immediate proximity of strong magnetic or electromagnetic fields or trans-

mission aerials. These can affect the measurement.

 

•   Prior to and after each measurement, check your instrument and the measuring leads for 

damages. Never take any measurements if the protecting insulation is defective or the 

measuring instrument is damaged otherwise.

VERSION 10/17

  •   Be especially careful when dealing with voltages higher than 50 V/AC or 75 V/DC. Even at 

such voltages you can get a life-threatening electric shock if you come into contact with live 

electric wires.

 

•   The measuring instrument is suitable for use in dry or damp conditions. Avoid use in a damp 

or wet environment.

 

•   Always ensure that the probe tips are perfectly clean. Dirty or even corroded test clips can 

lead to an incorrect measurement.

 

•   The test probes must only be touched at the handles provided for this purpose. Otherwise, 

there is danger of an electric shock.

 

•   Never exceed the highest permissible voltage values. If the stated values are exceeded, the 

product becomes damaged and poses a hazard that can be fatal. (See chapter “Technical 

data”).

 

•   The recovery time as specified in “Technical data” must always be adhered to. Otherwise, the 

product could be damaged.

 

•   The voltage values specified are nominal voltages.

 

•   If the neutral wire (N) or the earth wire (PE) is interrupted, no reading is shown.

 

•   The measuring instrument must only be used within the permissible ambient conditions (see 

chapter “Technical data”).

 

•   Always attach the measuring tip cover if you are no longer using the device.

 

•   Store the measuring instrument in a dry place, protected against dust, if you are no  longer 

using it.

 

•   When using the voltage tester in the measurement category CAT III and CAT IV, it is recom-

mended to attach the plastic protective covers to the test probes to decrease the length of the 

free contact tips. This reduces the risk of a possible short circuit during testing.

 

 •   Depending on the internal impedance of the voltage tester, there are different ways of 

displaying “operating voltage present” or “operating voltage not present” in the presence of 

interference voltage.

 

•   A voltage tester with relatively low internal impedance does not display all interference 

voltages with an initial value above ELV, compared to the reference value of 100 kΩ. Upon 

contact with the parts to be tested, the voltage tester may temporarily reduce the interference 

voltage by discharging to a level below ELV; however, after removing the voltage detector, the 

interference voltage will assume its original value again.

 

•   When the notification “voltage present” does not appear, it is strongly recommended that you 

insert the earthing device before starting work.

 

•   A voltage tester with relatively high internal impedance will not clearly display “operating 

voltage present” in the event of existing interference voltage, compared to the reference value 

of 100 kΩ.

 

•   When “voltage present” appears on a part which is considered disconnected from the system, 

it is strongly recommended to check the state “operating voltage not present” with additional 

measures (e.g., using a suitable voltage tester, visual inspection of the disconnection point in 

the electrical network, etc.) to make sure the voltage indicated by the voltage tester is not a 

fault.

 

•   A voltage tester indicating two values of the internal impedance has passed the design test 

for handling interference voltages and is able to differentiate (within technical limits) the 

operating voltage from the interference voltage and directly or indirectly display the existing 

voltage type.

 

CAT I 

 Measurement Category I is applicable to measuring circuits of electrical and electronic equip-

ment that is not directly supplied with mains voltage (battery-operated devices, etc.) 

CAT II 

 Measurement Category II is applicable to measuring circuits of electrical and electronic equip-

ment that is directly supplied with the mains voltage via a power plug. This category also 

covers all smaller categories (e.g. CAT I for measuring signal and control voltages).

CAT III 

 Measurement Category III is applicable to measuring circuits of installations in buildings (e.g. 

electric sockets or sub-distributions). This category also covers all smaller categories (e.g. 

CAT II for measuring electronic devices).

CATIV 

 Measurement Category IV is applicable to measuring at the origin of the low-voltage installa-

tion (e.g. main distribution, electricity provider’s transfer points to homes, etc.) and outdoors. 

This category also contains all lower categories.

GENERAL BATTERY INSTRUCTIONS

•   Batteries should be kept out of the reach of children.
•   Do not leave batteries lying around in the open; there is a risk of them being swallowed by children or 

pets. If they are swallowed, consult a doctor immediately.

•   Leaking or damaged batteries can lead to caustic burning of the skin. Therefore, use suitable protective 

gloves.

•   Batteries must not be short-circuited, opened or thrown into fire. There is a risk of explosion.
•   Make sure that the polarity is correct when inserting the batteries (pay attention to plus/+ and minus/–).

Summary of Contents for 1313886

Page 1: ...t Verätzungen verursachen benutzen Sie deshalb in diesem Fall geeignete Schutzhandschuhe Batterien dürfen nicht kurzgeschlossen zerlegt oder ins Feuer geworfen werden Es besteht Explosions gefahr Achten Sie beim Einlegen der Batterien auf die richtige Polung Plus und Minus beachten D BEDIENUNGSANLEITUNG VC64 ZWEIPOLIGER SPANNUNGSPRÜFER BEST NR 1313886 BESTIMMUNGSGMÄSSE VERWENDUNG Der 2polige Spann...

Page 2: ...läche um Kratzspu ren zu vermeiden SYMBOLBESCHREIBUNGEN Wechselspannung AC V AC DC V AC Wechselspannung V DC Gleichspannung 12 24 36 50 120 230 400 690 Anzeige des Nennspannungsbereichs in Volt V Gleichspannung Pluspotential DC Gleichspannung Minuspotential DC kΩ Elektrischer Widerstand in Kilo Ohm Hz Elektrische Frequenz Hertz Einpolige Phasenanzeige von 100 690 V sowie Warnung vor gefähr licher ...

Page 3: ...Power On 12 V DC AC Ansprechzeit 1 s Widerstandsmessbereich 0 19 99Ohm Max Messzeit RCD Test 30 s Regenerationszeit RCD Test 240 Sekunden Max Prüfstrom RCD Test 30 mA 230V Max Strom ohne RCD Last 3 5 mA 690V Messkategorie CAT IV 600 V CAT III 1000 V Normen EN 60529 und EN 61243 3 2014 Schutzart IP64 Verschmutzungsgrad 2 Temperaturbereich 15 C bis 45 C Luftfeuchte max 85 relative Feuchte nicht kond...

Page 4: ...ncorrect measurement The test probes must only be touched at the handles provided for this purpose Otherwise there is danger of an electric shock Never exceed the highest permissible voltage values If the stated values are exceeded the product becomes damaged and poses a hazard that can be fatal See chapter Technical data The recovery time as specified in Technical data must always be adhered to O...

Page 5: ...n after replacing the batteries the product must not be used Additional self test function all LED TORCH BUZZER are ON for 2 sec is implemented for all Conrad VTs It can be started when VT is off The user need to push Torch button 15 and hold for 4 sec After that all LED symbols light Torch light and buzzer sound is active for 2 sec Always attach the measuring tip cover if you are no longer using ...

Page 6: ...us substances are labelled with the symbol opposite indicating that disposal in the domestic waste is forbidden The symbols of the critical heavy metals are Cd Cadmium Hg Mercury Pb Lead You can return your used batteries rechargeable batteries free of charge to the official collection points in your municipality in our stores or anywhere batteries or rechargeable batteries are sold TECHNICAL DATA...

Page 7: ... point d interconnexion des entreprises d approvisionnement en élec tricité et en extérieur Cette catégorie comprend également toutes les catégories inférieures CONSIGNES GÉNÉRALES POUR LES PILES Gardez les piles hors de la portée des enfants Ne laissez pas les piles traîner les enfants ou les animaux domestiques pourraient les avaler En cas d ingestion consultez immédiatement un médecin Des piles...

Page 8: ...les Si même après le remplacement des piles aucune fonction n est disponible le produit ne doit plus être utilisé Pour un autotest de l appareil de mesure veuillez procéder comme suit avec l appareil éteint appuyez sur la touche d éclairage de la pointe de mesure 15 pendant environ 4 secondes Tous les LED sym boles l éclairage de l emplacement de mesure et le signal sonore sont actifs pendant envi...

Page 9: ...erdit de les jeter dans les ordures ménagères Les piles rechargeables contenant des substances nocives sont marquées par le symbole ci contre qui signale l interdiction de les jeter dans une poubelle ordinaire Les désignations pour les principaux métaux lourds dangereux sont Cd cadmium Hg mercure Pb plomb Vous pouvez rapporter gratuitement vos piles usagées aux centres de récupération de votre com...

Page 10: ... liggen het gevaar bestaat dat kinderen of huisdieren ze inslikken Raad pleeg in geval van inslikken onmiddellijk een arts Lekkende of beschadigde batterijen kunnen bij contact met de huid bijtend letsel veroorzaken draag daarom in dat geval geschikte beschermende handschoenen Sluit batterijen niet kort demonteer ze niet en gooi ze niet in het vuur Er bestaat explosiegevaar Let bij het plaatsen va...

Page 11: ... vervangen van de batterijen nog steeds niet functioneert mag het product niet worden gebruikt Voor een zelftest van het meetinstrument gaat u als volgt te werk druk in uitgeschakelde toestand gedurende ongeveer 4 seconden de toets van de meetpuntenbelichting 15 in Alle LED s symbolen de meetpuntenbelichting en de bieper zijn gedurende 2 seconden actief Plaats altijd de afdekking op de meetsondes ...

Page 12: ...iet toegestaan Batterijen met schadelijke stoffen worden aangegeven met het hiernaast afgebeelde pictogram dat op het verbod van afvoeren met gewoon huisvuil duidt De aanduidingen voor de betref fende zware metalen zijn Cd cadmium Hg kwik Pb lood Verbruikte batterijen kunt u gratis inleveren bij de inzamelpunten in uw gemeente of bij verkooppunten van batterijen en accu s TECHNISCHE GEGEVENS Spann...

Reviews: