background image

28 

 

  

  

  

No Spark at 
Electrode (fire not 
igniting pilot 
burner) 

Check ignition cable for 
damage and listen and 
watch for tracking out of 
spark to see if it is present 
but not making it to the 
electrode tip on the pilot 
burner. 

If cable damaged, 
replace cable. Reset 
error by performing 
a normal start cycle 
and try to start 
again. Replace pilot 
if necessary. 

  

  

  

Pilot pipe or pilot 
injector could be 
blocked 

Clear pipe and consider 
changing pilot 

  

E01 

Low current from 
thermocouple but 
flame: possibly CO 
alarm 

Flashing Red LED 
on TESC Control 

Pilot pipe blocked - 
no gas reaching 
pilot burner 

Check pilot pipe, check 
flame appearance of pilot 
flames 

  

  

  

  

Chimney blocked 
causing Co / Co2 to 
build up in the 
room 

Check flue 

  

  

  

  

Pilot thermocouple 
defective / old 

Change pilot or 
thermocouple 

  

  

  

  

Possible 
temporary air 
disturbance on 
pilot flame 

Clear error and restart to 
check ignition ok 

  

 

Code 

Comment 

Appearance 

Possible Cause 

Action 

  

E02 

too high ambient 
temperature ( >73 °C) 
around control 

  

Negative flue pull or 
blocked flue or 
similar 

Occurs if started ok 
then subsequently 
loss of thermocouple 
current. Check for 
flue problems. Fire 
cuts out to prevent 
over heating 

Reset and try again 

  

  

  

Blocked flue 

Check and clear 

Reset and try again 

  

  

  

Poor position of 
Ceramic parts 

Check manual for 
correct placement 

Reset and try again 

E03 

no, defective, or bad 
connected 
thermocouple 

  

Bad connection 

Check if connected 
are correct and 
terminals are sound 

Reset and try again 

  

  

  

defective 
thermocouple 

Replace Pilot 

Reset and try again 

E04 

false flame signal 

  

occurs during 
stopping fire 

Sensing flame on 
pilot when no flame 
should be there. 
Investigate. 

Reset and try again 

E05 

false flame signal 

  

Flame sensing on 
pilot before start of 
ignition sequence or 
after valve has shut 
off.    Contamination 
of electrode to 
ground 

Check if and clean 
around the area of 
the pilot for lint and 
other contamination 
and clean. Check 
where the 
thermocouple 
connect to the TESC 
control for the same 
contamination. Clean 
these areas. 

Reset and try again 

E06 

too low voltage on 
power supply to start 
the burner 

  

Weak or old or 
defective batteries 

Replace batteries 

Reset and try again 

Summary of Contents for 860HE

Page 1: ...860 Apex 860 Installation and User Instructions All instructions must be handed to user for safekeeping This is not a DIY product and must be installed by a Gas Safe registered installer Edition D 11...

Page 2: ...installer must be used for this purpose Read all these instructions before any installation takes place and in conjunction with the appliance on site This appliance must be installed in accordance wi...

Page 3: ...ted out Check that the components supplied correlate with the component checklist below If for some reason any of the listed components are missing or damaged do NOT commence with this installation in...

Page 4: ...Opening 13 7 2 Fitting the Burner Tray 14 8 Fuel Bed 14 9 Fitting The Outer Frame Trim 15 10 Commissioning the Appliance 15 10 1 Spark Failure 16 11 Setting Pressure 16 12 Spillage Monitoring System...

Page 5: ...ns issued by the Scottish Development Department BS 4543 part2 BS 5440 parts 1 2 BS 5871 part 32 BS 6461 parts 1 2 BS 6891 BS 8303 Failure to comply with these regulations could lead to prosecution an...

Page 6: ...ive height of at least three metres as measured from the hearth to the top of the flue Any flue damper plates or restrictors must be removed and no other restriction fitted to the flue Where removal i...

Page 7: ...h 322 Recess Height 460 Recess Width 875 Recess Depth 300 Air Vent N A Remote Valve TESCO01 RF868 15 Remote Pilot Assembly Thermocouple OXP PG 82 370 Slide Valve TESA3173 011 Pilot Assembly Thermocoup...

Page 8: ...place opening should be inspected and repairs made where necessary The dimensional requirements for debris collection space and spigot clearances are met See diagram below This appliance requires a na...

Page 9: ...material or any combustible material within 350mm must be clad with a non combustible board The correct clearances to combustible materials i e false chimney breast etc must be adhered to The manufact...

Page 10: ...appliance The fireplace opening and environment must be in compliance with specifications laid down in the appropriate sections of these instructions Remove the appliance from its carton as described...

Page 11: ...pellet all of the smoke should be drawn up the flue and exit correctly from the terminal If problems are found DO NOT fit the fire until corrective measures have been completed At this point if requi...

Page 12: ...opening at this point fix the fire box into place and pass the liner through the opening in the box connect to the flue adaptor supplied to the liner using self tapping screws and aluminium sealing ta...

Page 13: ...for installation of the fire the gas supply can be routed and when in the correct position can be connected to the isolation tap via the 8mm compression fitting DO NOT install or use the appliance wi...

Page 14: ...have the slide contoled version then you can place the slide control piece inposition using the two scews supplied Fit the two brackets supplier to each side of the firebox with self tapping screws s...

Page 15: ...emoved the top place can be removed by the two brackets in place then gentle remove the side sections and the back to fit simply reverse the process Turn on and test the gas supply up to the fire for...

Page 16: ...ire shuts down during use for no apparent reason then several things may be suspected if a door or window has been opened creating a draught then pilot disturbance is the problem and removal of the dr...

Page 17: ...ower front edge of the top of the fire as shown below in Fig 1 All smoke generated should be drawn back into the flue If slight spillage occurs or if in doubt repeat the test after a further 5 10 minu...

Page 18: ...hat the fire is fitted with a spillage safety device O D S If the fire shuts down this system may be in operation If spillage is suspected SWITCH APPLIANCE OFF and call in the installer to investigate...

Page 19: ...n for further details on clearances to combustibles No combustible material or flooring should protrude onto the hearth DO NOT burn any foreign material on this fire the coals must be of the correct t...

Page 20: ...e burner can be adjusted up and down by pressing the or buttons To stop the fire simply press the power button again and the burner will stop If you are not intending to use the fire for a long period...

Page 21: ...n shown below Note the indicator at the bottom shows the battery condition of both the batteries in the hand set and in the fire control within the fire RC Remote Control FC Fire Control The control i...

Page 22: ...rogress to setting the day of the week Setting the day of the week Press and release the and buttons until the correct day of the week is shown on the display Mo Monday Tu Tuesday We Wednesday Th Thur...

Page 23: ...illuminate Keep it held to keep the control unlocked to enable operation of the buttons Then with the other hand touch and keep you finger on the power button for about 5 seconds Upon touching the po...

Page 24: ...Battery Indicator RC Handset FC Fire Control Light Sensor for Display Backlight To Change Mode Press to Decrease Flame Power Button In Range of the fire If missing out of range or fire switched off Ro...

Page 25: ...ow ready to pair 2 Pairing the Handset to the Fire Control After fitting the batteries as above and with the isolator slide switch on the TESC Fire control in the ON position simultaneously press and...

Page 26: ...trol The hand set can pair with other modules to o L Operate an electric light which is the dimmable in 9 steps o F operate an electric fan which can have 9 speed levels o A operate an auxiliary conta...

Page 27: ...10 times as necessary to see if this overcomes the issue as it may resolve itself eventually No gas on appliance inlet Check to see if gas is present at gas appliance inlet Check gas supply is on the...

Page 28: ...l Negative flue pull or blocked flue or similar Occurs if started ok then subsequently loss of thermocouple current Check for flue problems Fire cuts out to prevent over heating Reset and try again Bl...

Page 29: ...on across terminals or damaged wiring Disconnect wired thermostat if fitted and try a start if it works replace thermostat Reset and try again E12 open circuit on wired thermostat if used Check wiring...

Page 30: ...n E19 Infrared receiver defective if used Check connection of IR or damage replace if necessary IR eye Check if wired correctly and replace IR eye if necessary Reset and try again E20 Incorrect setup...

Page 31: ...should not be detected contamination of electrode circuit to ground Check if and clean around the area of the pilot for lint and other contamination and clean Check where the thermocouple connect to t...

Page 32: ...your interest to register your appliance with Sirocco as soon as possible BEFORE CONTACTING SIROCCO FOR SERVICE PLEASE READ THE FOLLOWING Sirocco is committed to customer care and service To ensure w...

Page 33: ...9 Further information contact details and email facilities are available through our website www siroccofires com SPARE PARTS If you need assistance or wish to purchase spare parts 08432 890102 Mon to...

Page 34: ...ration form relating to the installation of the product must be presented to the company in respect of any claim under this guarantee 4 A CP1 form must be completed on commissioning the appliance and...

Page 35: ...occo beforehand or removed from the installation prior to Sirocco inspecting 19 The guarantee will not cover an appliance that has been subsequently removed without Sirocco having the opportunity to i...

Page 36: ...tems must be provided at the time of making the claim 31 The service log found in the installation instructions must be completed by the service engineer at the time of the service and an appropriate...

Reviews: