background image

 

COMMISSIONING: CO AND COMBUSTION RATIO CHECK

 

 

 

 

 

 

 

 

 

 

SET BOILER TO MAXIMUM RATE 

In accordance with, section 7.3, set boiler to operate at maximum rate (full load condition). Allow sufficient time for combustion to 
stabilise. , insert analyser probe into air inlet sampling point.

Is O2 ≥20.6%
and CO2 < 0.2%? 

Verify flue integrity 

Analyser readings indicate 
that combustion products 
and inlet air are mixing. 
Further investigation of the 
flue is therefore required. 
Check that flue components 
are correctly assembled, 
fixed and supported as per 
boiler/flue instructions. 
Check that flue and flue 
terminal are not obstructed. 

Is O2 ≥20.6% 
and CO2 < 0.2%? 

CHECK CO AND 

COMBUSTION RATIO 

AT MAXIMUM RATE 

With boiler still set at 

maximum rate, insert 

analyser probe into flue 
gas sampling point. 

Allow readings to 

stabilise before 

di

Is CO less than 

350ppm AND 
CO/CO

ratio less 

than 0.004? 

YES 

N

YES 

NO 

Check all seals 

around the appliance 

burner, internal flue 

seals, door and case 
seals. Rectify where 
necessary. 

Is CO less 
than 350ppm 

AND 
CO/CO

ratio 

less than 
0.004? 

CHECK CO AND COMBUSTION 
RATIO AT MINIMUM RATE 

With boiler set at minimum rate, 
insert analyser probe into flue 
gas sampling point. Allow 
readings  to stabilise before 
recording.

NO 

Turn off appliance and 
call Vokera’s technical 
helpline for advice. 
The appliance must not 
be commissioned until 
problems are identified 
and resolved. 

Turn off appliance and call 
Vokera’s technical helpline 
for advice. 
The appliance must not be 
commissioned until 
problems are identified and 
resolved. If commissioning 
cannot be fully completed, 
the appliance must be 
disconnected from the gas 
supply in accordance with 
the GSIUR. 

NOTE: 

Check and record CO and 

combustion ratio at both 
maximum AND minimum rate 
before contacting the Vokera 

SET BOILER TO 

MINIMUM RATE 

In accordance with 

section 7.3, set 

boiler to operate at 

minimum rate (to 
minimum load 

condition).  Allow 

sufficient time for 

combustion to 

stabilise. 
 

YES 

Is CO < 350ppm 

and CO/CO

ratio 

less

 

than 0.004 ?

 

NO 

Boiler is operating satisfactorily 
No further actions required. 

Ensure test points are capped, boiler case is correctly replaced and all other commissioning procedures are completed. 
Complete Benchmark Checklist, recording CO and combustion ratio readings as required. 

NOTE 

The air/gas ratio valve is factory-set and must not be 
adjusted during commissioning unless this action is 
recommended, following contact with the Vokera 
technical help line. If any such adjustment is 
recommended and further checking of the boiler is 
required, the engineer must be competent to carry out 
this work and to use the flue gas analyser accordingly. 
If the boiler requires conversion to operate with a 
different gas family (e.g., conversion from natural gas 
to LPG) separate guidance will be provided by the 
Vokera technical help line and must be followed. 

NO 

BEFORE CO AND COMBUSTION RATIO CHECK

The installation instructions should have been followed, gas 
type verified and gas supply pressure/rate checked as required 
prior to commissioning. 
As part of the installation process, 

ESPECIALLY WHERE A 

FLUE HAS BEEN FITTED BY PERSONS OTHER THAN THE 
BOILER INSTALLER
, visually check the integrity of the whole 
flue system to confirm that all components are correctly 
assembled, fixed and supported. Check that the maximum flue 
lengths have not been exceeded and all guidance has been 

followed (e.g. Technical Bulletin 008).

 

The flue gas analyser should be of the correct type, as specified 
by BS 7967. 
Before use, the flue gas analyser should have been maintained 
and calibrated as specified by the manufacturer. The installer 
must have the relevant competence for use of the analyser. 
Check and zero the analyser 

IN FRESH AIR, as per analyser 

manufacturer’s instructions. 

YES 

YES 

Summary of Contents for Vibe 20 A G.C. N 41-094-84

Page 1: ...NS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Vibe High ef...

Page 2: ...8 Mounting on a combustible surface 11 3A 9 Timber framed buildings 11 3A 10 Inhibitors 11 3A 11 Declaration of conformity 11 Installation Page 4 1 Delivery 12 4 2 Contents 12 4 3 Unpacking 12 4 4 Pr...

Page 3: ...er has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some time to r...

Page 4: ...ating temperature selector move the selector clockwise to increase the heating outlet temperature or counter clockwise to reduce the tem perature range 40 C 80 C for standard central heating The autom...

Page 5: ...t simultaneously 2 6 AUTOMATIC TEMPERATURE CONTROL The automatic temperature control function SARA permits the boiler when the heating temperature selector is set within 4 and 6 sector to automaticall...

Page 6: ...I NEED TO CALL AN ENGINEER Ifyouthinkyourboilermayhavedevelopedafault pleasecontact yourinstallerorVok raCustomerServices 08443910999 UK or 056 7755057 ROI have all your details to hand including ful...

Page 7: ...e ap plications These appliances are designed for use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It i...

Page 8: ...bytheelectroniccircuittoensureflamestability at the burner Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15minutes Thereafter theboil...

Page 9: ...Dry weight kg 26 28 2 5 Clearances Vibe 20A Vibe 25A Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 150mm Front 600mm 2 6 Connections Vibe 20A Vibe 25A Flow...

Page 10: ...wall 300 mm P From a structure to the side of the vertical terminal 300 mm Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar of the vertical terminal R To...

Page 11: ...an unusually high water content it may be necessary to provide additional expansion capacity see 6 18 3 6 6 FILLING POINT A method for initial filling of the system and replacing water lost during ser...

Page 12: ...is no requirement for a sheet of fireproof material to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefittedinaccordancewiththeIns...

Page 13: ...omplies with the local water authority regulations 3A 6 7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a positi...

Page 14: ...e see 2 9 Areduction must also be made to the maximum length see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1...

Page 15: ...ING THE REAR FLUE fig 14 rear flue outlet only Using the template provided mark and drill a 125mm hole for the passage of the flue pipe The hole should be drilled LEVEL to ensure any condense fluid th...

Page 16: ...rminal 1 0 metre 359 Twin adapter kit N A 531 Pitched roof flashing plate N A 532 Flat roof flashing plate N A 0225815 Condensate drain kit N A 0225820 0 25m extension pair 50mm 0225825 0 5m extension...

Page 17: ...iance flue outlet Remove the blanking plate located to the left of the appliance flue outlet and using the same screws install the air inlet plate B Using the hole in the exhaust connection manifold a...

Page 18: ...e wire to NEUTRAL supply green yellow to EARTH connection Insertthesupplied3 AMPfuseintothefusedisolatororfusedplug Should the fly lead be unsuitable refer to 4 7 3 for details on how to connect the e...

Page 19: ...nce service valves are open 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on Ensure any external controls are switched to an ON position and are calling for heat Move...

Page 20: ...ilure to install and com mission the appliance to the manufacturers instructions will invalidate the warranty 5 13 INSTRUCTING THE USER Hand over all documentation supplied with this appliance includi...

Page 21: ...from the pump assembly and remove the AAV assembly J Replace in the reverse order 6 7 1 TOP AUTOMATIC AIR RELEASE VALVE fig 29 Carry out component removal procedure as described in 6 4 Remove the AAV...

Page 22: ...tly ease the fan assembly out of its location Once the assembly has been removed the burner K1 can be withdrawn from the heat engine Ensure the seals L1 is in good condition taking care to ensure it i...

Page 23: ...s described in 6 4 Remove the locking pin Q1 that secures the cover R1 to the hydraulic manifold Using a hooked piece of wire carefully withdraw the by pass cartridge S1 Ensure all seals are in good c...

Page 24: ...the ignition sequence com mences Ignition is sensed by the electronic circuit to ensure flame stability at the burner Once successful ignition has been achieved the electronic circuitry increases the...

Page 25: ...it the plug fig 40 L2 and move the mode selector through position Remove the test probe from the test point and refit the sealing screw s and or cap IMPORTANT A GAS TIGHTNESS CHECK MUST BE CARRIED OUT...

Page 26: ...as failed but no fault is in dicated a detailed continuity check will be required to trace the fault A visual inspection of components may also assist in locating the fault 7 7 3 POLARITY CHECK With t...

Page 27: ...LICATIONS The appliance can be used with the following controls twin channel programmers The appliance can be used in conjunction with typical S Plan systems and Y Plan systems Please contact Vokera t...

Page 28: ...sed JP5 Selection operating only heating JP6 Unused JP7 Unused JP8 Closed Unused LED Led 1 green working status or temporary stop Led 2 yellow CO 2 function ON Led 3 red boiler lock out brown CN3 blue...

Page 29: ...INSTALLATION The entire installation including the meter must be purged and checked for gas tightness 9 6 2 GAS VALVE MAXIMUM SETTING Set the CO button at maximum see 10 3 1 once the maximum is obtai...

Page 30: ...TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio less...

Page 31: ...commissioning checklist completed in full To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation To maintain the boiler guarante...

Page 32: ...nterlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Page 33: ...egister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate...

Page 34: ...33...

Page 35: ...34...

Page 36: ...1HG enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limite...

Reviews: