background image

14

IMPORTANT

The vertical flue terminal is 1.0 metre in length and cannot be 

cut; therefore it may be necessary to adjust the height of the 
appliance to suit or use a suitable extension.

Connect the vertical flue assembly to the boiler flue spigot us

-

ing the 100mm clip, gasket & screws (supplied), ensuring the 

correct seal is made. The flue support bracket (supplied with 

the vertical flue kit) can now be fitted. 

If the vertical flue requires extension/s or additional bend/s, 

connect the required number of flue extensions or bends (up 

to the maximum equivalent flue length) between the boiler and 

vertical flue assembly (see fig. 13).

Ensure that any horizontal sections of the flue system have a 

minimum 1º; maximum 3º fall back to the boiler (1º = 17mm 
per 1000mm).

NOTE

When cutting an extension to the required length, you must en-
sure that the excess is cut from the plain end of the extension. 

Remove any burrs, and check that any seals are located properly.

You must ensure that the entire flue system is properly sup

-

ported and connected.

4.5.3 TWIN FLUE SYSTEM

The Vokèra twin flue system enables greater flue distances 

to be achieved than that of a concentric flue system. It can be 

used for horizontal or vertical applications, however the twin 

flue  system  must  be  converted  to  the  dedicated  concentric 

flue kit for termination. It is essential that the installation of the 

twin flue system be carried out in strict accordance with these 

instructions.

GUIDANCE NOTES ON TWIN FLUE INSTALLATION

•  The flue must have a have a minimum 1º; maximum 3º (1º 

= 17mm per 1000mm) fall back to the appliance to allow 

any condensate that may form in the flue system to drain 

via the condensate drain. Consideration must also be given 
to the fact that there is the possibility of a small amount of 
condensate dripping from the terminal.

•  Ensure that the entire flue system is adequately supported, 

use at least one bracket for each extension.

•  As the exhaust outlet pipe can reach very high temperatu

-

res it must be protected to prevent persons touching the hot 
surface.

•  The condensate drain pipe must be connected in accordan

-

ce with building regulations.

Reduction for bends

  Bend  

Reduction in maximum flue length for  

 

each bend

 

  45º bend 

1.0 metre 

  90º bend 

1.5 metre 

Twin flue accessories

  

Part No. 

Description 

Length

  0225805 

Horizontal flue terminal 

1.0 metre

  0225810 

Vertical flue terminal 

1.0 metre

  359 

Twin adapter kit 

N/A 

  531 

Pitched roof flashing plate 

N/A 

  532 

Flat roof flashing plate 

N/A 

  0225815 

Condensate drain kit 

N/A 

  0225820 

0.25m extension  (pair) 

50mm 

  0225825 

0.5m extension (pair) 

00mm 

  0225830 

1.0m extension (pair) 

1000mm

  0225835 

2.0m extension (pair) 

2000mm

  0225840 

45º bend (pair) 

N/A 

  0225845 

90º bend (pair) 

N/A 

  0225850 

Twin bracket (5) 

N/A 

  0225855 

Single bracket (5) 

N/A 

MOUNTING THE BOILER

The fixing holes for the wall-mounting bracket should now be 

drilled and plugged, an appropriate type and quantity of fixing 

should be used to ensure that the bracket is mounted securely.  
Once the bracket has been secured to the wall, mount the ap-
pliance onto the bracket.

4.5.2 CONCENTRIC VERTICAL FLUE

The appliance can be used with either the Vokèra condensing 

60/100mm concentric flue system or the optional 80/125mm 

concentric flue system.

NOTE

These instructions relate 

only

 to the Vokèra condensing 

60/100mm concentric flue system. For specific details on the 

installation of the 80/125mm concentric flue system please re

-

fer to the instructions supplied.

The vertical flue terminal can be connected directly to the ap

-

pliance flue outlet. Alternatively, an extension or bend can be 

connected to the appliance flue outlet if desired, however if 

additional bends are fitted, a reduction must be made to the 

maximum flue length (see table below).

Reduction for bends

 

 Bend                Reduction in maximum flue length for each bend

  45º bend 

1.0 metre (60/100) - 1.0 metre (80/125)

  90º bend 

1.0 metre (60/100) - 1.5 metre (80/125) 

Vertical flue terminal and accessories

  

Part No. 

Description  

Length

 

  29450122  Vertical flue terminal  

1000mm 

  531 

Pitched roof flashing plate 

N/A 

  532 

Flat roof flashing plate 

N/A 

  29450123 

90-degree bend 

N/A 

  29450124 

45-degree bends (pair) 

N/A 

  29450125 

500mm extension 

500mm 

  29450126 

1000mm extension 

1000mm 

  29450127 

2000mm extension 

2000mm 

  29450128 

Telescopic extension 

372/519mm

  529 

Wall bracket pack (5) 

208mm

Using the dimensions given in fig. 11 as a reference, mark and 

cut a 125mm hole in the ceiling and/or roof.

Fig. 17

“X”

12/15/20HE = 202mm
25/30/35HE = 218mm

130mm

Fit the appropriate flashing plate to the roof and insert the ver

-

tical flue terminal through the flashing plate from the outside, 

ensuring that the collar on the flue terminal fits over the flashing.

The fixing holes for the wall-mounting bracket should now be 

drilled and plugged, an ‘appropriate type and quantity of fixing 

should be used to ensure that the bracket is mounted securely. 
Once the bracket has been secured to the wall, mount the ap-
pliance onto the bracket.

Summary of Contents for Vibe 20 A G.C. N 41-094-84

Page 1: ...NS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Vibe High ef...

Page 2: ...8 Mounting on a combustible surface 11 3A 9 Timber framed buildings 11 3A 10 Inhibitors 11 3A 11 Declaration of conformity 11 Installation Page 4 1 Delivery 12 4 2 Contents 12 4 3 Unpacking 12 4 4 Pr...

Page 3: ...er has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some time to r...

Page 4: ...ating temperature selector move the selector clockwise to increase the heating outlet temperature or counter clockwise to reduce the tem perature range 40 C 80 C for standard central heating The autom...

Page 5: ...t simultaneously 2 6 AUTOMATIC TEMPERATURE CONTROL The automatic temperature control function SARA permits the boiler when the heating temperature selector is set within 4 and 6 sector to automaticall...

Page 6: ...I NEED TO CALL AN ENGINEER Ifyouthinkyourboilermayhavedevelopedafault pleasecontact yourinstallerorVok raCustomerServices 08443910999 UK or 056 7755057 ROI have all your details to hand including ful...

Page 7: ...e ap plications These appliances are designed for use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It i...

Page 8: ...bytheelectroniccircuittoensureflamestability at the burner Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15minutes Thereafter theboil...

Page 9: ...Dry weight kg 26 28 2 5 Clearances Vibe 20A Vibe 25A Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 150mm Front 600mm 2 6 Connections Vibe 20A Vibe 25A Flow...

Page 10: ...wall 300 mm P From a structure to the side of the vertical terminal 300 mm Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar of the vertical terminal R To...

Page 11: ...an unusually high water content it may be necessary to provide additional expansion capacity see 6 18 3 6 6 FILLING POINT A method for initial filling of the system and replacing water lost during ser...

Page 12: ...is no requirement for a sheet of fireproof material to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefittedinaccordancewiththeIns...

Page 13: ...omplies with the local water authority regulations 3A 6 7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a positi...

Page 14: ...e see 2 9 Areduction must also be made to the maximum length see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1...

Page 15: ...ING THE REAR FLUE fig 14 rear flue outlet only Using the template provided mark and drill a 125mm hole for the passage of the flue pipe The hole should be drilled LEVEL to ensure any condense fluid th...

Page 16: ...rminal 1 0 metre 359 Twin adapter kit N A 531 Pitched roof flashing plate N A 532 Flat roof flashing plate N A 0225815 Condensate drain kit N A 0225820 0 25m extension pair 50mm 0225825 0 5m extension...

Page 17: ...iance flue outlet Remove the blanking plate located to the left of the appliance flue outlet and using the same screws install the air inlet plate B Using the hole in the exhaust connection manifold a...

Page 18: ...e wire to NEUTRAL supply green yellow to EARTH connection Insertthesupplied3 AMPfuseintothefusedisolatororfusedplug Should the fly lead be unsuitable refer to 4 7 3 for details on how to connect the e...

Page 19: ...nce service valves are open 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on Ensure any external controls are switched to an ON position and are calling for heat Move...

Page 20: ...ilure to install and com mission the appliance to the manufacturers instructions will invalidate the warranty 5 13 INSTRUCTING THE USER Hand over all documentation supplied with this appliance includi...

Page 21: ...from the pump assembly and remove the AAV assembly J Replace in the reverse order 6 7 1 TOP AUTOMATIC AIR RELEASE VALVE fig 29 Carry out component removal procedure as described in 6 4 Remove the AAV...

Page 22: ...tly ease the fan assembly out of its location Once the assembly has been removed the burner K1 can be withdrawn from the heat engine Ensure the seals L1 is in good condition taking care to ensure it i...

Page 23: ...s described in 6 4 Remove the locking pin Q1 that secures the cover R1 to the hydraulic manifold Using a hooked piece of wire carefully withdraw the by pass cartridge S1 Ensure all seals are in good c...

Page 24: ...the ignition sequence com mences Ignition is sensed by the electronic circuit to ensure flame stability at the burner Once successful ignition has been achieved the electronic circuitry increases the...

Page 25: ...it the plug fig 40 L2 and move the mode selector through position Remove the test probe from the test point and refit the sealing screw s and or cap IMPORTANT A GAS TIGHTNESS CHECK MUST BE CARRIED OUT...

Page 26: ...as failed but no fault is in dicated a detailed continuity check will be required to trace the fault A visual inspection of components may also assist in locating the fault 7 7 3 POLARITY CHECK With t...

Page 27: ...LICATIONS The appliance can be used with the following controls twin channel programmers The appliance can be used in conjunction with typical S Plan systems and Y Plan systems Please contact Vokera t...

Page 28: ...sed JP5 Selection operating only heating JP6 Unused JP7 Unused JP8 Closed Unused LED Led 1 green working status or temporary stop Led 2 yellow CO 2 function ON Led 3 red boiler lock out brown CN3 blue...

Page 29: ...INSTALLATION The entire installation including the meter must be purged and checked for gas tightness 9 6 2 GAS VALVE MAXIMUM SETTING Set the CO button at maximum see 10 3 1 once the maximum is obtai...

Page 30: ...TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio less...

Page 31: ...commissioning checklist completed in full To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation To maintain the boiler guarante...

Page 32: ...nterlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Page 33: ...egister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate...

Page 34: ...33...

Page 35: ...34...

Page 36: ...1HG enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limite...

Reviews: