background image

22

7.1 CHECKING APPLIANCE OPERATION

When carrying out any repairs or servicing to the appliance, 
the relevant commissioning procedure must be undertaken to 
ensure the continued safe operation of the appliance. Particular 
attention should be made to ensure gas tightness, water tight-
ness and the electrical integrity of the appliance.

7.2 APPLIANCE MODES OF OPERATION

NOTE

There must be sufficient system water pressure (min. 0.5 bar) 

to ensure the water pressure switch is activated. If there is in-

sufficient system pressure the pump and fan will be prevented 

from operating and the low-pressure fault code will be indicated.

7.2.1 SELECTOR SWITCH IN THE OFF POSITION

When the selector switch is in the OFF position, the following 
functions are active.

Active functions

:

• 

frost-protection system

• 

pump anti-block.

7.2.2 ON-BOARD FUNCTIONS

• 

CO FUNCTION:

 the CO function when activated, will allow 

the appliance to run at CH maximum, whilst a combustion 
analysis check or a mechanical gas valve calibration is being 
carried out. Whilst the CO function is active, all other functions 
are disabled (minimum power operating period, anti-cycle, 
set-point, etc). Once enabled, the CO function will remain 
active for a 15-minute period, or until the function is manually 
deactivated.

• 

FROST-PROTECTION: 

this function is only active when there 

are no requests for heating or HW. If the temperature drops 
below 5°C, the boiler will operate on minimum power until 
the temperature of the thermistors reaches 35°C . Thereafter 
the pump & fan will over-run for 30-seconds.

• 

ANTI-CYCLE FUNCTION:

 the anti-cycle function ensures the 

burner remains switched off for at least 3-minutes after the 
set-point hysterisis (set-point + 5-deg) for CH heat request.  

• 

PUMP ANTI-BLOCK FUNCTION: 

when there has been no 

heating or HW request for 24-hours, the anti-block cycle is 
activated. The pump will be activated for a period of 30-sec-
onds.

• 

SARA function:

 the SARA function permits the boiler (when 

the set-point is within the SARA range) to automatically adjust 

(raise) the heating flow outlet temperature should the room 

thermostat contacts remain closed for more that 20-minutes.

7.2.3 HEATING MODE

With the selector switch in the heating  & hot water position 
and any additional controls (time clock, programmer, room 
thermostat, etc.) calling for heat, the appliance will operate 
in the heating mode. The pump and fan will be activated via 

the flow temperature sensor. When the fan is sensed to be 

operating correctly (tacho signal), the ignition sequence com-
mences. Ignition is sensed by the electronic circuit to ensure 

flame stability at the burner. Once successful ignition has been 

achieved, the electronic circuitry increases the gas rate to 75% 
for a period of 15 minutes.
The speed of the fan and therefore the output of the boiler is 
determined by the temperature of the water sensed by the 

flow temperature sensor, consequently a high temperature at 

the flow sensor results in a lower fan speed. As the water tem

-

perature increases, the temperature sensors – located on the 

flow pipe of the boiler – reduce the fan speed via the electronic 

circuitry. Depending on the load, either the water temperature 
will continue to rise until the set point is achieved or the water 
temperature will fall whereby fan speed will increase relative to 
the output required. When the boiler has reached the set point 
(+ hysterisis), the burner will switch off. The built-in anti-cycle 
device prevents the burner from re-lighting for approximately 

3-minutes. When the temperature of the flow sensor falls below 

the set point (- hysterisis), the burner will re-light.

NOTE

If the spark/sensing electrode does not sense ignition the appli-
ance will re-attempt ignition a further 4-times then go to lockout. 
When the set-point has been reached (the position of the heating 
temperature selector) as measured at the primary thermistor, the 
appliance will begin the modulation phase whereby the fan and 
gas valve will continuously modulate to maintain the set-point.
If the temperature continues to rise and exceeds the set-point 
by 5°C (hysterisis), the burner will shut down. A new ignition 
sequence will be enabled when the 3- minute anti-cycle has 
been performed and the temperature at the primary thermistor 
has dropped 5°C (hysterisis) below the set-point.

ATTENTION

Gas type and appliance output 

must be set 

according to the 

specific appliance specification. Vokèra accepts no responsi

-

bility if the gas type is not correctly adjusted according to the 

respective appliance specification as detailed on the appliance 

data badge.

SECTION 7 - CHECKS, ADJUSTMENTS AND FAULT FINDING

Fig. 39

Y1

Z1

A2

A3

A4

6.20 FLUE COLLECTOR REMOVAL (fig. 39)

Carry out component removal procedure as described in 6.4. Re

-

move the air chamber front cover. Remove the heat exchanger 

as per 6.16. Locate and remove the screw (

Y1

) that secures 

the flue gas analysis test point cover (

Z1

). Disconnect the flues 

thermistor wiring connections. Locate and remove the 4 screws 
(

A2

).  Locate and remove the 2 screws (

A3

).  Gently ease the 

condensate collector (

A4

) out off its location. Gently ease the 

flue collector out off its location. Replace in the reverse order.

Summary of Contents for Vibe 20 A G.C. N 41-094-84

Page 1: ...NS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Vibe High ef...

Page 2: ...8 Mounting on a combustible surface 11 3A 9 Timber framed buildings 11 3A 10 Inhibitors 11 3A 11 Declaration of conformity 11 Installation Page 4 1 Delivery 12 4 2 Contents 12 4 3 Unpacking 12 4 4 Pr...

Page 3: ...er has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some time to r...

Page 4: ...ating temperature selector move the selector clockwise to increase the heating outlet temperature or counter clockwise to reduce the tem perature range 40 C 80 C for standard central heating The autom...

Page 5: ...t simultaneously 2 6 AUTOMATIC TEMPERATURE CONTROL The automatic temperature control function SARA permits the boiler when the heating temperature selector is set within 4 and 6 sector to automaticall...

Page 6: ...I NEED TO CALL AN ENGINEER Ifyouthinkyourboilermayhavedevelopedafault pleasecontact yourinstallerorVok raCustomerServices 08443910999 UK or 056 7755057 ROI have all your details to hand including ful...

Page 7: ...e ap plications These appliances are designed for use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It i...

Page 8: ...bytheelectroniccircuittoensureflamestability at the burner Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15minutes Thereafter theboil...

Page 9: ...Dry weight kg 26 28 2 5 Clearances Vibe 20A Vibe 25A Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 150mm Front 600mm 2 6 Connections Vibe 20A Vibe 25A Flow...

Page 10: ...wall 300 mm P From a structure to the side of the vertical terminal 300 mm Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar of the vertical terminal R To...

Page 11: ...an unusually high water content it may be necessary to provide additional expansion capacity see 6 18 3 6 6 FILLING POINT A method for initial filling of the system and replacing water lost during ser...

Page 12: ...is no requirement for a sheet of fireproof material to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefittedinaccordancewiththeIns...

Page 13: ...omplies with the local water authority regulations 3A 6 7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a positi...

Page 14: ...e see 2 9 Areduction must also be made to the maximum length see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1...

Page 15: ...ING THE REAR FLUE fig 14 rear flue outlet only Using the template provided mark and drill a 125mm hole for the passage of the flue pipe The hole should be drilled LEVEL to ensure any condense fluid th...

Page 16: ...rminal 1 0 metre 359 Twin adapter kit N A 531 Pitched roof flashing plate N A 532 Flat roof flashing plate N A 0225815 Condensate drain kit N A 0225820 0 25m extension pair 50mm 0225825 0 5m extension...

Page 17: ...iance flue outlet Remove the blanking plate located to the left of the appliance flue outlet and using the same screws install the air inlet plate B Using the hole in the exhaust connection manifold a...

Page 18: ...e wire to NEUTRAL supply green yellow to EARTH connection Insertthesupplied3 AMPfuseintothefusedisolatororfusedplug Should the fly lead be unsuitable refer to 4 7 3 for details on how to connect the e...

Page 19: ...nce service valves are open 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on Ensure any external controls are switched to an ON position and are calling for heat Move...

Page 20: ...ilure to install and com mission the appliance to the manufacturers instructions will invalidate the warranty 5 13 INSTRUCTING THE USER Hand over all documentation supplied with this appliance includi...

Page 21: ...from the pump assembly and remove the AAV assembly J Replace in the reverse order 6 7 1 TOP AUTOMATIC AIR RELEASE VALVE fig 29 Carry out component removal procedure as described in 6 4 Remove the AAV...

Page 22: ...tly ease the fan assembly out of its location Once the assembly has been removed the burner K1 can be withdrawn from the heat engine Ensure the seals L1 is in good condition taking care to ensure it i...

Page 23: ...s described in 6 4 Remove the locking pin Q1 that secures the cover R1 to the hydraulic manifold Using a hooked piece of wire carefully withdraw the by pass cartridge S1 Ensure all seals are in good c...

Page 24: ...the ignition sequence com mences Ignition is sensed by the electronic circuit to ensure flame stability at the burner Once successful ignition has been achieved the electronic circuitry increases the...

Page 25: ...it the plug fig 40 L2 and move the mode selector through position Remove the test probe from the test point and refit the sealing screw s and or cap IMPORTANT A GAS TIGHTNESS CHECK MUST BE CARRIED OUT...

Page 26: ...as failed but no fault is in dicated a detailed continuity check will be required to trace the fault A visual inspection of components may also assist in locating the fault 7 7 3 POLARITY CHECK With t...

Page 27: ...LICATIONS The appliance can be used with the following controls twin channel programmers The appliance can be used in conjunction with typical S Plan systems and Y Plan systems Please contact Vokera t...

Page 28: ...sed JP5 Selection operating only heating JP6 Unused JP7 Unused JP8 Closed Unused LED Led 1 green working status or temporary stop Led 2 yellow CO 2 function ON Led 3 red boiler lock out brown CN3 blue...

Page 29: ...INSTALLATION The entire installation including the meter must be purged and checked for gas tightness 9 6 2 GAS VALVE MAXIMUM SETTING Set the CO button at maximum see 10 3 1 once the maximum is obtai...

Page 30: ...TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio less...

Page 31: ...commissioning checklist completed in full To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation To maintain the boiler guarante...

Page 32: ...nterlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Page 33: ...egister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate...

Page 34: ...33...

Page 35: ...34...

Page 36: ...1HG enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limite...

Reviews: