The Vitesse modular system is a cost effective method of providing power and control for lighting installations in in-

dustrial, commercial and retail buildings. The system is designed for ease of installation: mains input is connected 

using the spacious wiring compartment; control inputs and outputs are pluggable using industry standard connectors. 

The modular approach allows for between 4 and 16 luminaires to be connected.

 

• 

The VITM4

-

2CH is a two channel, non

-

dimming distribution box for use in applications that require two independently 

switched lighting circuits, or lighting and ventilation circuits. For example this product is ideal for connection to a 2 

channel presence detector for separate window row switching. It has two live inputs, a common neutral and two 

switch inputs. 

 

VITM4

-

S

-

2CH

 

Vitesse modular starter for non

-

dimming systems

 

VITM4

-

E

-

2CH

 

Vitesse modular extender for non

-

dimming systems

 

Channel for channel nuts (zebs)

 

Removable gland plate with

 

3 x Ø20mm knockouts

 

3 x Ø20mm knockouts for rear 

cable entry

 

4 x key slots to accept M6 

(1/4”) 

fixings

 

BESA  box fixings

 

202mm

 

150mm

 

14

6mm

 

12

7mm

 

122mm

 

75mm

 

Fixing points

 

M6 

(1/4”)

 

Warning

. This device works at mains voltage. Be sure to take care when working with electricity.

 

• 

The box should be fixed on a smooth, flat surface or using drop rod fixings attached to channel nuts. 

 

• 

Ensure that there is easy access to the wiring compartment and all connectors once the box is in

-

situ.

 

Height 

-

 allow 150mm for total height of unit (including connectors and cable)

 

9 pole interface 

connector and lead 

supplied with 

detectors 

 

Channel 1

 

Channel 2

 

Channel 1

 

Channel 2

 

Overview

 

Vitesse Modular 4 

-

 2 Channel Switching Modules

 

Product Guide

 

System Components

 

Installation

 

VITM4

-

2CH

 

Install this way up 

The unit MUST be 
installed this way up 
to ensure good lock 
of cable plug to 
socket.

 

Summary of Contents for VITM4-2CH

Page 1: ...r starter for non dimming systems VITM4 E 2CH Vitesse modular extender for non dimming systems Channel for channel nuts zebs Removable gland plate with 3 x Ø20mm knockouts 3 x Ø20mm knockouts for rear cable entry 4 x key slots to accept M6 1 4 fixings BESA box fixings 202mm 150mm 146mm 127mm 122mm 75mm Fixing points M6 1 4 Warning This device works at mains voltage Be sure to take care when workin...

Page 2: ...clamps Permanent Live Neutral Supply in Earth Live 1 Switched Live 2 Switched On Off 1 On Off 2 Live 1 Supply in Live 2 Supply in Local lighting switch and local emergency test switch N E L Local emergency test switch Local lighting switch 1 Emergency test using central switch N E L Multiple boxes DO NOT WIRE ACROSS PHASES Central emergency test switch A local lighting switch may still be used whe...

Page 3: ...r is used to interrupt the power N E Wire link Sensor Detector lead needs to be ordered separately from the detector Order code VITM4 L3 2CH Where two detectors connect to a single box a dual lead is available VITM4 LD3 2CH CH1 and CH2 plugs are coded Ensure that the plugs are inserted correctly and do not apply excessive force L2 L1 L2 L2 L1 Central emergency test switch Local emergency test swit...

Page 4: ...ches mode as shown short push turns ON Long held push turns OFF 1 sec Allow a few minutes initial power on setup to take place before operation the switches See detector programming manual further information Presence detector connections Automatic on automatic off Absence detector connections Manual on automatic off Switch Noise Filtering Due to the noise filtering process there is a small delay ...

Page 5: ... luminaires are typically situated nearest the windows The luminaires will also switch with occupancy Channel 2 occupancy only The inner luminaires ie those furthest from the windows are switched with occupancy only Switch inputs One or two manual switches ie for luminaires on channels 1 and 2 can be used to manually override the lights on or off or in the case of absence detection activate the lu...

Page 6: ...6 This page intentionally left blank ...

Page 7: ...7 This page intentionally left blank ...

Page 8: ... 50Hz Terminal capacity 4mm2 in wiring compartment Temperature 0ºC to 35ºC Power Rating of system 16A Rating of each output 10A but limited on the detector output rating check datasheet of detector Compliance LVD 2014 35 EU For further compliance information visit www cpelectronics co uk compliance For lighting purposes only with suitable circuit protection For fixed wiring only Ref WD325 Issue 8 ...