All wiring should be mains rated.

 

• 

Remove wiring compartment cover. Wire the box using the diagrams 

below

 

On/off 1 and On/Off 2 

connect switches through to detectors

 

Switched live 

turns the lights on and off

 

• 

Use the cable clamps to secure the wiring or use cable glands (not 

supplied). The clamps can be split, and flipped over to clamp 

different cable diameters.

 

• 

Replace wiring compartment cover.

 

• 

Plug in the luminaires ensuring that the connector latches to the box.

 

• 

The unit MUST be installed orientated as per the arrow to ensure 

good lock of cable plug to socket!

 

 

 

Small

 

cables

 

Large 

cables

 

Cable clamps

 

Permanent  Live

 

Neutral

-

Supply in

 

Earth

 

Live 1

-

Switched 

 

Live 2

-

Switched

 

On / Off 1

 

On / Off 2

 

Live 1

-

Supply in

 

Live 2

-

Supply in 

 

Local lighting switch and local emergency test switch

 

N

 

E

 

L

 

Local emergency 

test switch

 

Local lighting 

switch 1

 

Emergency test using central switch

 

N

 

E

 

L

 

Multiple boxes

 

DO NOT WIRE ACROSS 

PHASES

 

Central 

emergency test 

switch

 

A local lighting switch may still be used when there 

is a central emergency test switch or when a circuit 

breaker is  used to interrupt the power.

 

Wire link

 

N

 

E

 

L

 

Wire link

 

Wire link

 

Channel 1

 

Channel 2

 

Local lighting 

switch 2

 

Emergency test using power interruption

 

Wiring

 

Wiring using single supply 

 

 

Luminaire connections / Lead colours

 

Permanent Live

 

Black (4 core only)

 

Neutral

 

Blue

 

Earth

 

Green / Yellow

 

Switched Live

 

Brown

 

Install this way up

 

Summary of Contents for VITM4-2CH

Page 1: ...r starter for non dimming systems VITM4 E 2CH Vitesse modular extender for non dimming systems Channel for channel nuts zebs Removable gland plate with 3 x Ø20mm knockouts 3 x Ø20mm knockouts for rear cable entry 4 x key slots to accept M6 1 4 fixings BESA box fixings 202mm 150mm 146mm 127mm 122mm 75mm Fixing points M6 1 4 Warning This device works at mains voltage Be sure to take care when workin...

Page 2: ...clamps Permanent Live Neutral Supply in Earth Live 1 Switched Live 2 Switched On Off 1 On Off 2 Live 1 Supply in Live 2 Supply in Local lighting switch and local emergency test switch N E L Local emergency test switch Local lighting switch 1 Emergency test using central switch N E L Multiple boxes DO NOT WIRE ACROSS PHASES Central emergency test switch A local lighting switch may still be used whe...

Page 3: ...r is used to interrupt the power N E Wire link Sensor Detector lead needs to be ordered separately from the detector Order code VITM4 L3 2CH Where two detectors connect to a single box a dual lead is available VITM4 LD3 2CH CH1 and CH2 plugs are coded Ensure that the plugs are inserted correctly and do not apply excessive force L2 L1 L2 L2 L1 Central emergency test switch Local emergency test swit...

Page 4: ...ches mode as shown short push turns ON Long held push turns OFF 1 sec Allow a few minutes initial power on setup to take place before operation the switches See detector programming manual further information Presence detector connections Automatic on automatic off Absence detector connections Manual on automatic off Switch Noise Filtering Due to the noise filtering process there is a small delay ...

Page 5: ... luminaires are typically situated nearest the windows The luminaires will also switch with occupancy Channel 2 occupancy only The inner luminaires ie those furthest from the windows are switched with occupancy only Switch inputs One or two manual switches ie for luminaires on channels 1 and 2 can be used to manually override the lights on or off or in the case of absence detection activate the lu...

Page 6: ...6 This page intentionally left blank ...

Page 7: ...7 This page intentionally left blank ...

Page 8: ... 50Hz Terminal capacity 4mm2 in wiring compartment Temperature 0ºC to 35ºC Power Rating of system 16A Rating of each output 10A but limited on the detector output rating check datasheet of detector Compliance LVD 2014 35 EU For further compliance information visit www cpelectronics co uk compliance For lighting purposes only with suitable circuit protection For fixed wiring only Ref WD325 Issue 8 ...

Reviews: