4. Programming
D-307083 PowerMaster-360R Installer's Guide
57
Option
Configuration instructions
02:ENTRY ALARM
Define whether the system will report a confirmed alarm during an entry delay (see CONFIRM
ALARM below).
DD243
(default) - An alarm initiated by another detector during the entry delay is not regarded
as a confirmed alarm.
normal mode
- The control panel will report a confirmed alarm for the second alarm that is
triggered from a different zone within the confirmation time. There are no alarm restrictions
during entry delay or for the delay zone.
03:END EXIT MODE
Define how the exit delay is terminated or restarted according to the following options:
door/fob only
- When the door is closed, or by pressing the AUX button on the keyfob
1
,
whichever first.
restart>reentry
- Exit delay restarts when the door is reopened during exit delay. The restart
occurs once only. Restarting the exit delay is helpful if the user re-enters immediately after
going out to retrieve an item that was left behind.
door/fob/timer
- When the door is closed, by pressing the AUX button on the keyfob
1
, or when
the exit delay has expired, whichever first.
fob/timer
(default) - By pressing the AUX button on the keyfob
1
, or when the exit delay has
expired, whichever first.
04:FOB/KP PANIC
Define the devices that cannot trigger a panic alarm.
DD243
(default) – KF-234 and KF-235 PG2.
all
- All devices can trigger a panic alarm
05:CONFIRM ALARM
Define a specific time period that if 2 successive alarms occur, the second alarm will be
considered as a
confirmed alarm
, (see RPT CNFM ALRM below).
Options:
in
30
/
45
/
60
(default)/
90
minutes
06:CONFIRM PANIC
A confirmed panic alarm is reported if one of the following occurs within the confirmation time:
a) A second panic device is activated.
b) A second panic alarm on the same device is activated.
c) A tamper event is activated (not from the zone / device that initiated the panic alarm).
Options:
in
4
/
8
/
12
/
20
(default)/
24 hours
and
disabled
07:RPT CNFM ALRM
Define whether the system will report a confirmed alarm.
enable + bypass
(default) - The system will report a confirmed alarm and will bypass all
alarmed open zones when the siren ends or when the confirmation timer expires.
disable
- The system will not report a confirmed alarm.
enable
- The system will report a confirmed alarm.
08:ENTRY DELAY 1
09:ENTRY DELAY 2
Two different entry delays allow the user to enter the protected site (while the system is in the
armed state) via 2 specific doors and routes without causing an alarm.
Following entry, the user must disarm the control panel before the entry delay expires. Slow-
rate warning beeps start sounding once the door is opened, until the last 10 seconds of the
delay, during which the beeping rate increases. Locations No. 1 (entry delay 1) and 2 (entry
delay 2) allow you to program the length of these delays.
Options:
10
/
15
/
30
(ENTRY DELAY 1
default
)/
45
/
60
(ENTRY DELAY 2
default
)
seconds
;
3
/
4 minutes
10:ABORT TIME
The PowerMaster-360R can be configured to provide a delay before reporting an alarm to the
monitoring station (not applicable to alarms from FIRE, 24H SILENT and EMERGENCY
zones). During this delay period, the siren sounds but the alarm is not reported. If the user
disarms the system within the delay time, the alarm is aborted. You can activate the feature
and select the Abort Time interval.
Options:
in 00
(default in USA)/
15
/
30
(default)
/45/60 seconds
;
in 2/3/4 minutes
11:CANCEL ALARM
The PowerMaster-360R can be configured to provide a Cancel Alarm time window that starts
1
Applies only when the keyfob is defined as skip exit delay (for further details, see the keyfob's User's Guide)