1.0 INSTALLATION INSTRUCTIONS
NOTE:
The installation should only be performed by an authorized gas fitter.
1.1 General instructions
The gas fireplace must be installed, connected and inspected as a balanced flue fire by a qualified fitter,
according to national, regional, and local standards and regulations.
The flue system and the terminals in the outer wall or roof face must also meet the requirements outlined
in the applicable standards and regulations.
The temperature of the walls and shelves near the side and back of the unit may not be more than 80°C
higher than the temperature of the environment.
The unit has been approved in combination with the THC CC Ø100 mm - Ø150 mm and Ø130 mm - Ø200
mm, in accordance with European CE standards for gas fires, and may therefore only be applied with this
flue system.
The product needs to be serviced and inspected by the fitter for local gas distribution as indicated on the
identification plate.
The instructions are only applicable if the relevant country code is stated on the unit. If this is not the case,
the gas technical information for the relevant country needs to be consulted and modifications discussed
with the manufacturer.
There will be air in the gas pipes when the unit is first used. The gas pipes therefore need to be purged
first.
Ignite the fire according to operating instructions and check whether the burner flame is uniform. After the
unit has been used for the first time, you should remove any deposits resulting from running/burning in
the paint, using a glass cleaner for heaters.
Distance to flammable materials:
With respect to the front, side and top of the unit, a distance of 1200 mm needs to be kept between the unit
and: curtains, floor covering, upholstery and fabrics, and/or other flammable material unless stated otherwise in
these instructions.
Distance to non-flammable materials:
The unit needs to be placed a minimum distance of 25 mm from the wall unless stated otherwise in these
instructions.
IMPORTANT: Never install the unit against or within a flammable wall.
NOTE:
Construction material for fireplaces and mantles etc. or built-in situation, must be made of non-
combustible material. This also applies to floors and ceilings. Never use flammable materials near the unit in
compliance with the above requirements. If in doubt, consult your dealer.
PAGE 3
Summary of Contents for TL73
Page 1: ...INSTALLATION INSTRUCTIONS FOR MODELS TL73 TL73H TL73T TL73RD ...
Page 20: ...APPENDIX 2 INSTALLATION EXAMPLES PAGE 21 1 2 3 4 MAX 1500 ...
Page 21: ...APPENDIX 2 INSTALLATION EXAMPLES PAGE 22 4 5 6 ...
Page 22: ...APPENDIX 3 PREPARATION AND INSTALLATION PAGE 22 1 1 2 3 4 5 6 7 ...
Page 27: ...APPENDIX 6 ARRANGEMENT OF VARIOUS BURNER FILLINGS PAGE 29 PEBBLES 1 2 ...