Technical Data
5.4.2.1 Digital input channels
GND-IO
IN-X
INx
GND
GND
Image 14: Schematic layout of digital input channels 1 to 16
Characteristics
•
Polarity protection
•
Galvanic decoupled
•
Inputs have ESD protection and interference signal filter
•
The input channels have a common GND connection (GND-IN).
Parameter
Parameter
Min
Nom
Max
Number of inputs
16
Input v VIN (DC)
0 V
24 V
30 V
(1)
Input voltage “Low”
0 V
14 V
Input voltage “High”
19 V
30 V
Input current V
in
= 24 V
2 mA
Input frequency at V
in
= 24 V
5 kHz
Galvanic decoupling
present
(1)
Higher input voltages destroy the respective input channel.