Virginia Controls, LLC
MH-3000 User Manual, 1_03C10-VC
Page 91
•
Enable Park With Doors Open
–
Turn on to make the car park with the doors open at
the Main Landing.
•
Enable Park With Doors Open at All Ldgs
–
Turn on to make the car park with the
doors open at all landings.
•
Use Negative Pressure Input for Flood Sw
–
Turn on to use the Negative Pressure
Switch Input for the Flood Switch. This will disable the Negative Pressure Sw operation,
and allow the Flood operation to be initiated by the Negative Pressure Sw Input. If a
Negative Pressure Sw is not used, the input may be jumped on (a factory jumper is
normally installed). If Flood operation is required, the Flood Switch may be connected
to the Low Oil Sw Input, with no changes required to the program or settings. If a Low
Oil Switch is already being used, then connect the Flood Sw to the Negative Pressure Sw
Input, and turn this setting on. If all three are required, check the schematic to see the
connection arrangements required for this specific job.
•
Disable Automatic Timed Jack Re-Synch
- Enable this bit feature to stop the
automatic Jack Re-synchronization. The Jack Re-synchronization will only operate when
the Jack Out-of-Synchronization Input turns on, if used. This feature is only used with
the Jack Resynchronization feature.
•
Do Jack Re-Synchronization When Inspection Sw Is Cycled
- Enable this bit
feature to initiate the automatic Jack Re-synchronization whenever the Inspection
Switch is turned from Inspection to Normal. This feature is only used with the Jack
Resynchronization feature.
•
Disable Negative Pressure Sw on Jack Resync
–
Turn this feature on to disable the
Negative Pressure Switch feature when the car is doing a Jack Re-Sync.
•
Enable Jack Out Of Synchronization Input
- Enable this bit feature to allow Jack Re-
synchronization to be initiated by the Jack Out Of Sync Input. This feature is only used
with the Jack Resynchronization feature.
•
Jack Re-Synchronization Time is in Hours not Days
- Enable this bit feature to
allow Jack Re-synchronization Time Base to be hours, not days. This may be used to
initiate Jack Re-Sync more often than once every day. If the time base is set as days,
then the resync will occur at midnight. If it is set as hours, it will occur whenever the
timer trips.
•
Disable Fault Latch Feature
–
Turn this feature on to disable the feature that latches
faults. Faults are latched for compliance with the 2010 and later codes. If this feature is
NOT turned on, then faults must be reset by jumping the Fault Reset Input or by turning
on Sw4 on the CPU Dip Sw block. With this feature on, faults can be reset by cycling
power or by cycling the Inspection Sw.
•
Manual Reset on Redundancy and Door Zone Faults
- Enable this bit feature to
require Redundancy and Door Zone faults to be reset manually. Cycling power will not
reset those faults. This feature is used in conjunction with the Latched Fault feature
described above.
•
Disable Reset at Intermediate Floors
- Enable this bit feature to disable position
resets at intermediate floors. The car will still reset at terminal landings, based on the
Door Zone input and the Up or Down Slowdown inputs.