Transfer rate and DeviceNet address
With PowerOFF there is the possibility to specify the
Transfer rate
respectively the
DeviceNet-Address
and then to activate these with
PowerON.
Note!
Changes of the transfer rate respectively of the DeviceNet address were
only recognized after PowerON or an automatic reset.
Changes during the normal operation are not recognized.
Every station on the DeviceNet communicates with the same transfer rate.
The setting of the transfer rate happens with the following proceeding:
•
Switch the power supply to PowerOFF.
•
Set switch 1 to "1" (Configuration).
•
Preset the transfer rate with switch 2 ... 4.
No. Description
Example
1 Configuration
1
2 Transfer rate 125kBit/s
0
3 Transfer rate 250kBit/s
1
4 Transfer rate 500kBit/s
0
5 -
-
6 -
-
7 -
-
C
1
2
4
8
16
32
--
1
0
1
2
3
4
5
6
7
8
8 not
used
-
Transfer rate:
250kBit/s
•
Switch on the power supply. The preset transfer rate is stored in the
EEPROM. Your DeviceNet coupler now uses this transfer rate.
With an successful storage the RD LED (green) gets on.
With a wrong setting of the transfer rate the SF LED (red) lights up.
Overview
Setting the
transfer rate
LED indication
RD LED
SF LED
Summary of Contents for SLIO IM 053-1DN00
Page 1: ...VIPA System SLIO IM 053 1DN00 Manual HB300E_IM RE_053 1DN00 Rev 11 21 May 2011...
Page 4: ...Contents Manual VIPA System SLIO ii HB300E IM RE_053 1DN00 Rev 11 21...
Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E IM RE_053 1DN00 Rev 11 21...
Page 28: ...Chapter 1 Basics and Assembly Manual VIPA System SLIO 1 20 HB300E IM RE_053 1DN00 Rev 11 21...