![VIPA SLIO IM 053-1DN00 Manual Download Page 21](http://html1.mh-extra.com/html/vipa/slio-im-053-1dn00/slio-im-053-1dn00_manual_1029236021.webp)
Manual VIPA System SLIO
Chapter 1 Basics and Assembly
HB300E - IM - RE_053-1DN00 - Rev. 11/21
1-13
If the 10A for the power section supply is no longer sufficient, you may use
the power module from VIPA with the order number 007-1AB00. So you
have also the possibility to define isolated groups.
The power module with the order number 007-1AB10 is to be used if the
3A for the electronic power supply at the backplane bus is no longer
sufficient. Additionally you get an isolated group for the DC 24V power
section supply with 4A.
By placing the power module 007-1AB10 at the following backplane bus
modules may be placed with a sum current of max. 2A. Afterwards the
power module 007-1AB10 is to be placed again.
To secure the power supply, the power modules may be mixed used.
007-1AB00
Sys DC 5V: ---
DC 24V: 10A
007-1AB00
Sys DC 5V: ---
DC 24V: 10A
DC24V
0V
DC24V
0V
DC24V max. 10A
SysDC5V max. 3A
DC24V max. 10A
DC24V max. 10A
DC24V
0V
DC24V
0V
1
2
1
1
007-1AB10
Sys DC 5V: 2A
DC 24V: 4A
007-1AB10
Sys DC 5V: 2A
DC 24V: 4A
DC24V
0V
DC24V
0V
DC24V max. 10A
SysDC5V max. 3A
SysDC5V max. 2A
SysDC5V max. 2A
DC24V max. 4A
DC24V max. 4A
DC24V
0V
DC24V
0V
1
2
3
3
DC24V
0V
4
DC24V
0V
4
(1) DC 24V for power section supply I/O area (max. 10A)
(2) DC 24V for electronic power supply bus coupler and I/O area
(3) DC 24V for power section supply I/O area (max. 4A)
(4) DC 24V for electronic power supply I/O area
Deployment of the
power modules
Power module
007-1AB00
Power module
007-1AB10
Summary of Contents for SLIO IM 053-1DN00
Page 1: ...VIPA System SLIO IM 053 1DN00 Manual HB300E_IM RE_053 1DN00 Rev 11 21 May 2011...
Page 4: ...Contents Manual VIPA System SLIO ii HB300E IM RE_053 1DN00 Rev 11 21...
Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E IM RE_053 1DN00 Rev 11 21...
Page 28: ...Chapter 1 Basics and Assembly Manual VIPA System SLIO 1 20 HB300E IM RE_053 1DN00 Rev 11 21...