Chapter 2 Power modules
Manual VIPA System SLIO
2-8
HB300E - PS-CM - Rev. 11/28
For wires with a cross section of 0.08mm
2
up to 1.5mm
2
.
2
6
3
7
4
8
1
5
1
2
3
4
5
6
7
8
2
6
3
7
4
8
1
5
PM
0V
DC24V
0V
DC24V
Sys
DC24V
0V
Pos.
Function
Type Description
1 --- ---
not
connected
2
DC 24V
I
Feed-in DC 24V
power section supply
3
0V
I
Feed-in ground GND
power section supply
4
Sys DC 24V
I
Feed-in DC 24V
electronic power supply
5 --- ---
not
connected
6
DC 24V
O
DC 24V power section supply I/Os
7
0V
O
ground GND power section supply I/Os
8
0V
I
Feed-in ground GND
electronic power supply
I: Input, O: Output
Note!
•
Power section and electronic power section supply are internally
protected against higher voltage by fuses. The fuses are within the
power module. If one fuse released, its electronic module must be
exchanged!
•
It is recommended to externally protect the power section supply with a
fast 4A fuse respectively by a line circuit breaker 4A characteristics Z
and the electronic power supply with a fast 1A fuse respectively by a line
circuit breaker 1A characteristics Z.
•
Please consider this module has no internal buffer concerning power
dips. To match to the standard EN 61131-2, a power supply unit should
be used, which can avoid power dips of up to 10ms.
Attention!
Please consider within wiring the maximum load current of the contacts.
With the System SLIO this is max. 10A.
Pin assignment
Summary of Contents for SLIO 001-1BA00
Page 1: ...VIPA System SLIO PS CM Manual HB300E_PS CM Rev 11 28 July 2011...
Page 4: ...Contents Manual VIPA System SLIO ii HB300E PS CM Rev 11 28...
Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E PS CM Rev 11 28...
Page 48: ...Chapter 3 Clamp modules Manual VIPA System SLIO 3 8 HB300E PS CM Rev 11 28...