Chapter 2 Power modules
Manual VIPA System SLIO
2-4
HB300E - PS-CM - Rev. 11/28
For wires with a cross section of 0.08mm
2
up to 1.5mm
2
.
2
6
3
7
4
8
1
5
1
2
3
4
5
6
7
8
2
6
3
7
4
8
1
5
PM
0V
DC24V
0V
DC24V
Pos.
Function
Type Description
1 --- ---
not
connected
2
DC 24V
I
Feed-in DC 24V
power section supply
3
0V
I
Feed-in ground GND
power section supply
4 --- ---
not
connected
5 --- ---
not
connected
6
DC 24V
O
DC 24V power section supply I/Os
7
0V
O
ground GND power section supply I/Os
8 --- ---
not
connected
I: Input, O: Output
Attention!
Since the power section supply is not internally protected, it is to be
externally protected with a fuse, which corresponds to the maximum
current. This means max. 10A is to be protected by a 10A fuse (fast)
respectively by a line circuit breaker 10A characteristics Z!
Please consider within wiring the maximum load current of the contacts.
With the System SLIO this is max. 10A.
Pin assignment