Chapter 4 Deployment
Manual VIPA Accessories
4-18
HB37E - IM - RE_306-1LE00 - Rev. 09/28
Via the
Identifier related diagnostic
you gain information at which slot
(module) an error has occurred.
More detailed information about the error is available via the
Module state
and the
Channel related diagnostic
.
The
Identifier related diagnostic
may be activated via the parameterization
and has the following structure:
Identifier related diagnostic
Byte
Bit 7 ... Bit 0
X
Bit 5 ... 0: 000101 (fix) Length of the
Identifier related diagnostic
Bit 7 ... 6: 01 (fix) Code for
Identifier related diagnostic
X+1
The bit is set if one of the following occurs:
- a module is removed
- a module is connected, which is not configured
- a connected module may not be accessed
- a module reports a diagnostic interrupt
Bit 0: Entry for module at slot 1
Bit 1: Entry for module at slot 2
Bit 2: Entry for module at slot 3
Bit 3: Entry for module at slot 4
Bit 4: Entry for module at slot 5
Bit 5: Entry for module at slot 6
Bit 6: Entry for module at slot 7
Bit 7: Entry for module at slot 8
X+2
Bit 0: Entry for module at slot 9
Bit 1: Entry for module at slot 10
Bit 2: Entry for module at slot 11
Bit 3: Entry for module at slot 12
Bit 4: Entry for module at slot 13
Bit 5: Entry for module at slot 14
Bit 6: Entry for module at slot 15
Bit 7: Entry for module at slot 16
X+3
Bit 0: Entry for module at slot 17
Bit 1: Entry for module at slot 18
Bit 2: Entry for module at slot 19
Bit 3: Entry for module at slot 20
Bit 7 ... 4: reserved
Identifier related
diagnostic