CP143
H1 / TCP/IP manual
The CP143 H1 / TCP/IP network board
Rev. 00/07
4-25
Bit 7: Disable / enable blocking of data
Set:
by the user: to prevent overwriting of a block of data by the RECEIVE-
module or to stop transmission of a data block by the SEND-module (only for
the first data block).
Reset:
by the user: to release the respective data block.
Check:
by means of handler modules SEND and RECEIVE. When bit 7 is set these
modules will not transfer any data and indicate to the CP that an error has
occurred.
•
•
•
•
Error management byte 2, bit 0 to bit 3
This location contains the error flags returned by a task. The error flags are only valid when the
bit “Task completed with errors” in the status bit is set as well.
The following error messages are possible:
0
no error
If the “Task completed with errors” bit is set, then the CP143 H1 / TCP/IP has re-
established the connection, e.g. after a restart or a RESET.
1
incorrect Q/ZTYP at the HTB
The TYP-identifier for the task was incorrect.
2
The specified area does not exist in the PLC
The configuration of the DB (DBNR) for a task was incorrect.
3
The area in the PLC is too small
The sum of Q/ZANF and Q/ZLAE exceeds the limits of the area. The area-limits of data
modules is determined by the size of the module. The limits for flags, timers, counters, etc.
depend on the PLC.
4
QVZ-error in the PLC
The source or destination parameters refer to an area in the PLC that contains defective
memory or no memory at all. The error QVZ can only occur for Q/ZTYP AS, PB, QB or
when memory has been damaged.
5
Error in the indicator word.
The configured indicator word can not be processed. This error may occur when ANZW
refers to a data word or double word that never did or is no longer located in the specified
data module. That is, the DB is too small or does not exist.
6
no valid ORG format
The destination or the source for the data was not specified, neither in the handler module
(Q/TYP="NN") nor in the connection module.
7
Reserved
8
no unused transport connections
The capacity for transport connections has been exceeded. Please delete unnecessary
connections.
Summary of Contents for CP143 TCP/IP
Page 2: ...Lerrzeichen ...
Page 10: ...Lerrzeichen ...
Page 16: ...Lerrzeichen ...
Page 24: ...TCP IP protocol CP143 H1 TCP IP manual 2 8 Rev 00 07 ...
Page 26: ...LerrzeicLerrzeichenhen ...
Page 46: ...Standards and specifications CP143 H1 TCP IP manual 3 20 Rev 00 07 ...
Page 48: ...Lerrzeichen ...
Page 80: ...Lerrzeichen ...
Page 158: ...Application in combination with TCP IP CP143 H1 TCP IP manual 5 78 Rev 00 07 ...
Page 160: ...LerrzLerrzeicheneichen ...
Page 194: ...Lerrzeichen ...
Page 196: ...Technical data CP143 H1 TCP IP manual A 2 Rev 00 07 ...
Page 202: ...List of abbreviations CP143 H1 TCP IP manual C 2 Rev 00 07 ...
Page 206: ...List of tables CP143 H1 TCP IP manual E 2 Rev 00 07 ...