User Manual
Arctic Substation Gateway
Firmware Version 2.4.x
44
Document Version 1
IEC-101 retry limit
Value range
0-65000
Note
Cause of transmission length (IEC-101)
Defines the length of IEC-101 Cause of transmission ASDU header field in
bytes.
Table 46: IEC-101 ASDU cause of transmission length
IEC-101 ASDU cause of transmission length
Type
Field length
Units
Bytes
Value range
1-3
Note
The IEC-101 standard defines value 1.
Common address length (IEC-101)
Defines the length of the IEC-101 Common address ASDU header field in
bytes.
Table 47: IEC-101 ASDU common address length
IEC-101 ASDU common address length
Type
Field length
Units
Bytes
Value range
1-3
Note
The IEC-101 standard defines value 2.
Info object address length (IEC-101)
Defines the length of IEC-101 Information object address ASDU header field
in bytes.
Table 48: IEC-101 ASDU information object address length
IEC-101 ASDU information object address length
Type
Field length
Units
Bytes
Value range
1-3
Note
The IEC-101 standard defines value 2.
7.6
ASDU Converter
The ASDU converter can be used to convert ASDU header field lengths
between IEC-101 and IEC-104 protocols.