IEC-101 slave link address
Units
N/A
Value range
1-65000
Note
The link-level address of IEC-101 slave.
Link address field length
Defines the length of the IEC-101 link-level address field in bytes.
Table 39: IEC-101 slave link address field length
IEC-101 slave link address field length
Type
Field length
Units
Bytes
Value range
1, 2
Note
The link-level address of IEC-101 slave.
Event poll interval
It defines the IEC-101 event polling interval in 0.1 second increments (class 1
or 2 poll).
Table 40: IEC-101 event poll interval
IEC-101 event poll interval
Type
Interval
Units
0.1 seconds
Value range
1-65000
Note
The events are polled only when the
IEC-104 connection is active.
Link test interval
It defines the IEC-101 link test interval in 0.1 second increments. Link test is
performed if there is no other activity.
Table 41: IEC-101 link test interval
IEC-101 link test interval
Type
Interval
Units
0.1 seconds
Value range
1-65000
Note
The link test is performed if there is no
other activity during defined interval.
Keep link open
Defines that the IEC-101 link is kept always open even when there is no active
IEC-104 connection. If the functionality is enabled the Arctic sends link test