6
SL24.T
EN
ENCB
OFF
When the motor is operating: second encoder channel signal absent (encoder not working)
ON
When the motor is operating: second encoder channel present (it flashes very fast, depending on the motor rotation
speed)
31
OFF
Limit switch 1 contact (RH magnet-holder bracket) open (limit switch engaged)
ON
Limit switch 1 contact (RH magnet-holder bracket) closed (limit switch engaged)
32
OFF
Limit switch 2 contact (LH magnet-holder bracket) open (limit switch engaged)
ON
Limit switch 2 contact (LH magnet-holder bracket) closed (limit switch not engaged)
51
OFF
Step-by-step input (term. 51) not engaged
ON
Step-by-step input (term. 51) engaged
52
OFF
Pedestrian input (term. 52) not engaged
ON
Pedestrian input (term. 52) engaged
61
OFF
Stop contact (term. 61) open (engaged)
ON
Stop contact (term. 61) closed (not engaged)
62
OFF
Closing photocell (term. 62) engaged
ON
Closing photocell (term. 62) not engaged
63
OFF
Photocell or safety edge (term. 63) open (engaged)
ON
Photocell or safety edge (term. 63) closed (not engaged)
Gate travel calibration
NOTE: To perform this procedure, the gate must be stationary.
CAUTION! THE SAFETY DEVICES ARE DISABLED DURING GATE TRAVEL CALIBRATION.
Before performing calibration, check the direction of the motor (DIP 10 = OFF, opening to the left, DIP 10 = ON opening to the right).
APERTURA
APERTURA
ON
1 2 3 4 5 6 7 8 9 10
DIP1
ON
1 2 3 4 5 6 7 8 9 10
DIP1
Quick calibration
(slow-down at 50 cm during opening and 75 cm during closing, pedestrian opening at 1 metre)
No. Press
push-button Step
Description
1
-
Preparation
Move the gate to approximately 1 metre from closing
2
PROG
Procedure activation
Press the programming pushbutton PROG for at least 3 seconds, until the PRG LED starts flashing
slowly, and then release it
3
51
Gate closing
Press pushbutton 51: the motor closes at reduced speed up to the closing limit switch
4
-
Gate opening
The motor opens at reduced speed up to the opening limit switch
5
-
Gate closing
The motor closes at normal speed up to the closing limit switch
6
-
End of procedure
The PRG LED turns off. End of procedure
OPENING