Wiring for accessories not supplied
When the pressure set point is given by the CVF type remote control or the 0-10V output, the factory-fit
-
ted potentiometer in the controller must be disconnected.
When the speed set point is given by the MODBUS BMS the factory-fitted potentiometer in the controller
must be disconnected,
as well as the shunt between terminals 13 and 15.
CVF
ON/ OFF
1
2
3
4
5
P
Power supply (V)
Output signal GN
D
18 19
+24
V
Start
/
Stop
Start/ Sto
p
8
7
10
+5V
An1
GN
D
CVF
Instead of
the potentiometer
Instead
of the
shunt
Controller
0 - 10V OUTPUT
0-10V
Output
Controller
7 8
GN
D
An
1
13
+24V
*
12VDC Maxi Output signal
GN
D
Sensor power supply
*24Vdc -
40mA Maxi
MODBUS
Controller
20 21
A
B
RS + 485
RS - 485
18
ON / OFF
Controller
Controller
Controller
+24V
ON / OFF command
Instead of
the shunt
19
4
5
6
NO
COM
NC
Relay fault
5A/250VAC breaking capacity
*0-10V output examples: temperature sensor, humidity sensor.
No 24V power supply if BMS connection.
For a BMS, controlling is only done by the 0-10V signal and GND.
Gas actuator output contact
BDRA
16 17
Fire
+24V
Thermo switch
N/F
11
22
33
12
21
34
Factory fitted
and wired
5.7.2 Adjusting the pressure set point
By potentiometer, CVF type remote control or 0-10V output.
By default the roof fan is set to obtain the pressure in bold in the table.
The potentiometer in the controller allows you to change the pressure set point.
The set point can be given by a CVF type remote control or a 0-10V output.
Correspondence table between the potentiometer graduation, the voltage applied on terminal 7 and the
pressure set point.
Note
: After each adjustment wait 1 minute for the fan speed to stabilize.
Potentiometer
graduation
Voltage (in V) at
terminal 7
Without display
Voltage (in V) at
terminal 7
With display*
0
0
0 Pa
0
0 Pa
1
0,5
0 Pa
0,5
80 Pa
2
1
100 Pa
1
160 Pa
3
1,5
200 Pa
1,5
240 Pa
4
2
300 Pa
2
320 Pa
5
2,5
400 Pa
2,5
400 Pa
6
3
500 Pa
3
480 Pa
7
3,5
600 Pa
3,5
560 Pa
8
4
700 Pa
4
640 Pa
9
4,5
800 Pa
4,5
720 Pa
10
5**
800 Pa
5**
800 Pa
*If the roof fan has a display, the display will show you the pressure measured at the roof fan plate (see diagram below).
**If 0-10V source, 5 to 10V: 800Pa.