![ViM KUBAIR F400 ECOWATT CC Technical Manual Download Page 27](http://html1.mh-extra.com/html/vim/kubair-f400-ecowatt-cc/kubair-f400-ecowatt-cc_technical-manual_1026856027.webp)
27/44
NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
5.6.2
Adjusting the flow rate set point,
By potentiometer, CVF type remote control or 0-10V output.
Adjustment of the flow rate set point by potentiometer, CVF type remote control or 0-10V output.
The potentiometer in the controller allows you to change the flow rate set point.
The display under the cap shows the calculated flow rate.
For Sizes 355 / 400 / 450
: the display shows m
3
/h.
Graduation
potentiometer
Flow rate (m
3
/h)
355
400
450
0
0
0
0
1
2040
3050
3340
2
2880
4320
4720
3
3530
5290
5780
4
4080
6100
6680
5
N/A
N/A
7460
Graduation
potentiometer
Flow rate (m
3
/h)
355
400
450
6
N/A
N/A
8170
7
N/A
N/A
N/A
8
N/A
N/A
N/A
9
N/A
N/A
N/A
10
N/A
N/A
N/A
N/A : max. flow rate already reached
Note
: After each adjustment wait 1 minute for the fan speed to stabilize.
By Modbus BMS
The flow rate set point can be given by a Modbus BMS set point. To find the settings of the Modbus con
-
nection, refer to § "5.2.4 Modbus connection - Connection to a BMS".
After you wired your Modbus link:
Turn on the power to connect yourself to the controller. The roof fan wheel must be stopped.
Steps
Register numbers
Value to be entered
1 - Access to Level 1
5
1
2 - Change in the operating mode of the controller
6
9
3 - Saving of changes
5
10000
4 - Changing the set point
16
Between 0 and 1,000 to define the desired
flow rate set point, see the table below
Register set point 16
KUBAIR
®
F400 ECOWATT
®
355
KUBAIR
®
F400 ECOWATT
®
400
KUBAIR
®
F400 ECOWATT
®
450
100
2 040 m
3
/h
3 050 m
3
/h
3 340 m
3
/h
200
2 880 m
3
/h
4 320 m
3
/h
4 720 m
3
/h
300
3 530 m
3
/h
5 290 m
3
/h
5 780 m
3
/h
400
4 080 m
3
/h
6 100 m
3
/h
6 680 m
3
/h
500
N/A
N/A
7 460 m
3
/h
600
N/A
N/A
8 170 m
3
/h
700
N/A
N/A
N/A
800
N/A
N/A
N/A
900
N/A
N/A
N/A
1000
N/A
N/A
N/A
For information, calculation of the air flow rate according to the set point:
Q
v
= K x
√
2,5 x set point, with K the fan coefficient.
Size of KUBAIR
®
F400 ECOWATT
®
Coeff. K
355
129
400
193
450
211