Speed adjustment 0 / LS / HS (adjustable LS)
The adjustment can be done by a BCCA type 2S 0 / LS / HS switch.
The low speed is adjusted with the controller potentiometer.
The high speed is the roof fan speed with a control signal of 10V.
Speed adjustment 0 / LS / HS (adjustable LS and HS)
The adjustment can be done with a VRPZ voltage variator.
The low speed and the high speed are adjusted with the VRPZ, see VRPZ operating instructions.
Speed adjustment by the Modbus BMS
The adjustment can be done with a Modbus BMS . To know the parameters of the Modbus connection,
refer to § "5.2.4 Modbus connection - Connection to a BMS".
After you wired your Modbus Link:
Turn on the power to connect yourself to the controller. The roof fan wheel must be stopped.
Steps
Register numbers
Value to be entered
1 - Access to Level 1
5
1
2 - Change in the operating mode of the controller
6
2
3 - Saving of changes
5
10000
4 - Changing the set point
0
Between 1000 and 10,000 to set the
desired speed of the roof fan, see the
table below
Fan stop
0
0
Register set point 0
KUBAIR
®
F400 ECOWATT
®
355
KUBAIR
®
F400 ECOWATT
®
400/450
1000
200 rpm
200 rpm
2000
380 rpm
345 rpm
3000
560 rpm
490 rpm
4000
740 rpm
630 rpm
5000
920 rpm
780 rpm
6000
1 110 rpm
920 rpm
7000
1 290 rpm
1 070 rpm
8000
1 470 rpm
1 210 rpm
9000
1 650 rpm
1 360 rpm
10000
1 830 rpm
1 500 rpm
5.6 KUBAIR
®
F400 ECOWATT
®
Single-phase - CAV constant flow rate control
During operation at constant flow rate, the controller regulates the speed of the roof fan to obtain the set
point flow rate. A display installed under the cap indicates the flow rate measured in m
3
/h. The flow rate
set point can be adjusted by the potentiometer in the controller, by a CVF ON/OFF + variation remote
control, by an external 0-10V output or by Modbus BMS.