24/44
NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
Wiring for regulation according to the deviation between the set point / external measurement
0 - 10V
Output
Controller
12VDC Maxi output signal
GND
Sensor power supply
*24Vdc -
40mA Maxi
0 - 10V OUTPUT
11 12 13
An
2
GND +24V*
14 15
Speed-Output
GND
Shunt
ON/
OFF
1
2
3
4
5
P
Power supply (V) Output signal
GND
18 19
+24V
Start/Stop
CVF
Instead of
the potentiometer
Instead of the shunt
Controller
*0-10V output examples: temperature sensor, humidity sensor.
No 24V power supply if BMS connection.
For a BMS, controlling is only done by the 0-10V signal and GND.
CVF
7
8
GND
An
1
10
+5
V
5.5.2 Speed adjustment (unregulated VAV)
By potentiometer, or CVF type remote control.
By default the roof fan is set to its maximum speed, in bold in the table below.
The potentiometer in the controller allows you to change the speed of the turbine to adjust the flow rate.
The adjustment can be done with a CVF type remote control.
Correspondence table between the graduation of the internal potentiometer, the voltage applied on ter-
minal 9 and the speed.
Graduation
potentiometer
Voltage (V)
at terminal 9
KUBAIR
®
F400 ECOWATT
®
355
KUBAIR
®
F400 ECOWATT
®
400/450
0
0
200 rpm
200 rpm
2
1
530 rpm
460 rpm
4
2
850 rpm
720 rpm
6
3
1 180 rpm
980 rpm
8
4
1 500 rpm
1 240 rpm
10
5
1 830 rpm
1 500 rpm
For information: The flow rate is proportional to the speed of rotation.
Q
v2
= Q
v1
x
(
N
2
)
N is the speed of rotation.
N
1
By 0-10V output
Correspondence table between the voltage applied on terminal 7 and the speed.
Voltage (V)
at terminal 7
KUBAIR
®
F400 ECOWATT
®
355
KUBAIR
®
F400 ECOWATT
®
400/450
0
200 rpm
200 rpm
2
530 rpm
460 rpm
4
850 rpm
720 rpm
6
1 180 rpm
980 rpm
8
1 500 rpm
1 240 rpm
10
1 830 rpm
1 500 rpm