NT-50906901-KSDR-ECOWATT-48-88-120-AN-170907
63/68
ENGLISH
To perform the reboot, the CORRIGO
must be powered on; power the unit
by turning the proximity switch.
Using a fi ne rod (trombone type)
reboot the CORRIGO.
Clip the CORRIGO to the DIN rail by
reversing the unclipping operation,
without reconnecting the connectors
except for the command control.
From the command control, perform the following operations:
Advance parameters
Application
System
Communication
Time / Date
CORRIGO Ventilation
Expansion unit 1
Expansion unit 2
Preloaded Vtc-fi les
Title:
Preloaded Vtc-fi les
Activate ? No
2 min
Title:
Preloaded Vtc-fi les
Activate ?
Yes
Ventilation Vim
Choose Confi guration
Standard
Accept change :
No
Ventilation Vim
Choose Confi guration
KSDR 1
Accept change :
No
Ventilation Vim
Choose Confi guration
28ES 3P
Accept change :
Yes
The CORRIGO program is
being activeted
Advance parameters
Single air flow unit
2014-06-26
System : Start
C:22.0C R: 19.0°C
Menu
Continu the setting of the unit see:
Commissioning
Cut the electrical power supply, reconnect the connectors to the CORRIGO and close the unit.