1.  DESCRIPTION

Viking Quick Response Ordinary Hazard Dry Horizontal Sidewall Sprinklers are 

thermosensitive spray sprinklers suitable for use in areas subject to freezing. 

The sprinklers are designed for dry systems and preaction systems where it is 

necessary to prevent water or condensation from entering the drop nipple before 

sprinkler operation. They may also be installed in spaces subject to freezing 

and supplied from a wet system in an adjacent heated area. The large orifice 

dry sidewall sprinkler allows greater flows at lower pressures than standard 

orifice sprinklers. The newly desinged deflector carries an expanded approval for 

installation from 4” to 12” below the ceiling.
Viking Quick Response Ordinary Hazard Dry Horizontal Sidewall Sprinklers 

are available in various finishes and temperature ratings to meet design 

requirements. The special Polyester coating has been investigated for installation 

in corrosive atmospheres and is cULus listed as corrosion resistant as indicated 

in the Approval Chart. 

NOTE: When installed in some corrosive environments, the Polyester finish 

may change color. This natural discoloration over time is not in itself an 

indication of corrosion and should not be treated as such. All sprinklers 

installed in corrosive environments should be replaced or tested as 

described in NFPA 25 on a more frequent basis.

2.  LISTINGS AND APPROVALS

cULus Listed: 

Category VNIV

NYC Approved:

 MEA 89-92-E, Volume 37

Refer to the Approval Chart on page 3 and Design Criteria on page 4 for cULus Listing requirements that must be followed.

3.  TECHNICAL DATA

Specifications:

Available since 2005.

Minimum Operating Pressure: 7 PSI (0.5 bar) 

Maximum Working Pressure: 175 PSI (12 bar). 

Factory tested hydrostatically to 500 psi (34.5 bar)

Thread size: 1” NPT or 25 mm BSP

Nominal K-Factor: 8.0 U.S. (115.2 metric*) for lengths up to 48”. 

*  Metric K-factor measurement shown is when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

Covered by U.S. Patent numbers: 8,636,075 and 8,376,060

Material Standards:

Frame Casting: Brass UNS-C84400 

Deflector: Phosphor Bronze UNS-C51000

Fusible Element Assembly: Nickel Alloy

Trigger and Support: Stainless Steel UNS-S31600

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Compression Screw: Brass UNS-C36000

Seat and Adapter Assembly: Brass UNS-C36000

Orifice: Copper UNS-C11000 or UNS-C21000 

Tube: ERW Hydraulic Steel Tube

Inlet and Barrel End: QM Brass or Brass UNS-C31400 or Brass UNS-C31600

Support (Internal): Brass UNS-C36000 or Brass UNS-C31400 or Brass UNS-C31600 

Barrel: Steel Pipe UNS-G10260, Electrodeposited Epoxy Base finish

Sleeve (for Adjustable Standard style only): Brass UNS-C26000 or UNS-C26800

Replaces Form No. F_022717 Rev 18.1

(Added P65 Warning.)

Summary of Contents for VK2843

Page 1: ...olyester finish may change color This natural discoloration over time is not in itself an indication of corrosion and should not be treated as such All sprinklers installed in corrosive environments s...

Page 2: ...Horizontal Sidewall up to 62 1 575 mm Plain Barrel Dry Horizontal Sidewall up to 64 1 626 mm Contact the manufacturer for more information Finish Suffix Brass A Chrome F and White Polyester M W Temper...

Page 3: ...1 2 to 45 1 2 38 1 mm to 1 156 mm 2 Chrome or White Polyester with A dimensions 3 1 4 to 47 1 2 82 5 mm to 1 207 mm 3 Chrome or Brass with A dimensions 3 to 47 76 2 mm to 1 194 mm Footnotes 1 Part nu...

Page 4: ...Fusible Link Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers Designed for use in Light a...

Page 5: ...5 mm shorter than the A Dimension To locate the deflector at the maximum distance from the wall with no adjustment available order the standard dry horizontal sidewall sprinikler 1 25 mm longer than t...

Page 6: ...1 16 27 mm 5 Escutcheon outer diameter 3 1 16 78 mm 6 Top of deflector to centerline 5 8 16 mm Determining the A Dimension Adustable Recessed HSW Sprinkler with Model E 1 Escutcheon 1 Determine the d...

Page 7: ...to deflector distance 2 1 4 57 mm 4 Top of deflector to centerline 5 8 16 mm 5 Pipe outside diameter Same as 1 13 mm Schedule 40 pipe 1 5 16 33 mm Determining the A Dimension Plain Barrel Dry HSW Spri...

Page 8: ...eaded tee fitting per ANSI 16 4 Class 125 only Exposed Barrel Outer surface of wall Ambient Temperature of the Protected Area at the Discharge End of the Sprinkler Exposed Barrel Ambient Temperature 4...

Reviews: