Viking VK2843 Technical Data Manual Download Page 4

QUICK RESPONSE 

ORDINARY HAZARD DRY 

HSW FUSIBLE LINK  

SPRINKLERS (8.0K)  

(VK2843, VK2883, & VK2923)

TECHNICAL DATA

Page 4 of 8

Form No. F_022717     18.11.01     Rev 18.1.P65

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Figure 2:  Wrench 07565W/B for Adjustable Recessed Dry Horizontal Sidewall Sprinklers

** NOTE: A 1/2” ratchet is required and not available from Viking.

Sprinkler Wrench 

(Part No. 07565W/B)** for installing recessed dry sprinklers.

Step 1:  

Carefully slide the wrench sideways around 

the deflector and fusible link as shown.

Step 2:  

Press the wrench onto the sprinkler wrench 

flats and turn slightly to ensure engagement 

with the wrench flats.

DESIGN CRITERIA 

(Also refer to the Approval Chart on page 3.)

NOTE: When using CPVC fittings with Viking dry sprinklers, use only new Nibco Model 5012-S-Bl tees. When selecting other CPVC fittings, 

contact Viking Technical Services.
cULus Listing Requirements:

 

Quick Response Dry Horizontal Sidewall Fusible Link Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with 

the latest edition of NFPA 13 for standard spray sprinklers.

• 

Designed for use in Light and Ordinary Hazard occupancies with smooth, flat ceilings only. 

• 

Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13.

• 

Minimum spacing allowed is 6 ft. (1.8 m).

• 

Deflector must be positioned between 4” and 12” (102 mm and 305 mm) below the ceiling. Keep the top of the deflector oriented parallel with the 

ceiling.

• 

Locate no less than 4” (102 mm) from end walls.

• 

Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured 

perpendicular to the wall.

• 

The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed.

IIMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 

for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest 

edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza-

tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Summary of Contents for VK2843

Page 1: ...olyester finish may change color This natural discoloration over time is not in itself an indication of corrosion and should not be treated as such All sprinklers installed in corrosive environments s...

Page 2: ...Horizontal Sidewall up to 62 1 575 mm Plain Barrel Dry Horizontal Sidewall up to 64 1 626 mm Contact the manufacturer for more information Finish Suffix Brass A Chrome F and White Polyester M W Temper...

Page 3: ...1 2 to 45 1 2 38 1 mm to 1 156 mm 2 Chrome or White Polyester with A dimensions 3 1 4 to 47 1 2 82 5 mm to 1 207 mm 3 Chrome or Brass with A dimensions 3 to 47 76 2 mm to 1 194 mm Footnotes 1 Part nu...

Page 4: ...Fusible Link Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers Designed for use in Light a...

Page 5: ...5 mm shorter than the A Dimension To locate the deflector at the maximum distance from the wall with no adjustment available order the standard dry horizontal sidewall sprinikler 1 25 mm longer than t...

Page 6: ...1 16 27 mm 5 Escutcheon outer diameter 3 1 16 78 mm 6 Top of deflector to centerline 5 8 16 mm Determining the A Dimension Adustable Recessed HSW Sprinkler with Model E 1 Escutcheon 1 Determine the d...

Page 7: ...to deflector distance 2 1 4 57 mm 4 Top of deflector to centerline 5 8 16 mm 5 Pipe outside diameter Same as 1 13 mm Schedule 40 pipe 1 5 16 33 mm Determining the A Dimension Plain Barrel Dry HSW Spri...

Page 8: ...eaded tee fitting per ANSI 16 4 Class 125 only Exposed Barrel Outer surface of wall Ambient Temperature of the Protected Area at the Discharge End of the Sprinkler Exposed Barrel Ambient Temperature 4...

Reviews: