background image

QUICK RESPONSE 

ORDINARY HAZARD DRY 

HSW FUSIBLE LINK  

SPRINKLERS (8.0K)  

(VK2843, VK2883, & VK2923)

TECHNICAL DATA

Page 2 of 8

Form No. F_022717     18.11.01     Rev 18.1.P65

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Escutcheon Materials:

Adjustable Standard Dry Escutcheons: Brass UNS-C26000 or UNS-C26800

Recessed Dry Escutcheons: Cold Rolled Steel UNS-G10080

Ordering Information: (Also refer to the current Viking price list.)

Order Quick Response Ordinary Hazard Dry Horizontal Sidewall Sprinklers by first adding the appropriate suffix for the sprinkler 

finish, the appropriate suffix for the temperature rating, and then the suffix for the length (“A” dimension) to sprinkler base part 

number. Order in a specific length noted as the “A” dimension (see Figures 3, 5, and 6). The “A” dimension is the distance from 

the face of the fitting (tee) to the desired finished surface of the wall in which it is to be installed. 

These sprinklers are listed and approved in lengths from 1-1/2” to 45-1/2” (38 mm to 1,156 mm) for the Adjustable Standard style, 

3” to 47” (76 mm to 1,194 mm) for the Plain Barrel style, and 3-1/4” to 47-1/2” (83 mm to 1,207 mm) for the Adjustable Recessed 

style.

Lengths exceeding the standard lengths are available, with no approvals, on a “made-to-order” basis: Recessed Dry Horizontal 

Sidewall up to 64-1/2 (1,632 mm). Adjustable Standard Dry Horizontal Sidewall up to 62” (1,575 mm). Plain Barrel Dry Horizontal 

Sidewall up to 64” (1,626 mm). Contact the manufacturer for more information.

Finish Suffix: Brass = A, Chrome = F, and White Polyester = M-/W

Temperature Suffix: 165 °F (74 °C)= C, 205 °F (96 °C) = E, 280 °F (138 °C) = G

For example, sprinkler VK2923 with 1” NPT Threads, Chrome finish, 165 °F (74 °C) temperature rating, and “A” length of 10” = 

Part No. 21485FB10. 

Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: 

(Also refer to the Viking website.)

Sprinkler Wrenches:

A. Standard Wrench: Part No. 07297W/B (available since 1991) 

B. Wrench for recessed sprinklers: Part No. 07565W/B** (available since 1991)

  **A ½” ratchet is required (not available from Viking).

Dry Sprinkler Protective Cover: Part No. 15610

Replacement Escutcheons:

A. Adjustable Standard Dry Escutcheon: Base Part No. 08086F

B. Model E-1 Recessed Dry Escutcheon Cup: Base Part No. 05459A

4.  INSTALLATION

Refer to appropriate NFPA Installation Standards.

5.  OPERATION

During fire conditions, the heat-sensitive fusible element assembly disengages, releasing the internal parts to open the waterway. 

Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control 

the fire.

6.  INSPECTIONS, TESTS AND MAINTENANCE

Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.

7.  AVAILABILITY

The Viking Quick Response Ordinary Hazard Dry Horizontal Sidewall Sprinkler is available through a network of domestic and 

international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.

8.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Figure 1: Standard Sprinkler Wrench 

07297W/B

Summary of Contents for VK2843

Page 1: ...olyester finish may change color This natural discoloration over time is not in itself an indication of corrosion and should not be treated as such All sprinklers installed in corrosive environments s...

Page 2: ...Horizontal Sidewall up to 62 1 575 mm Plain Barrel Dry Horizontal Sidewall up to 64 1 626 mm Contact the manufacturer for more information Finish Suffix Brass A Chrome F and White Polyester M W Temper...

Page 3: ...1 2 to 45 1 2 38 1 mm to 1 156 mm 2 Chrome or White Polyester with A dimensions 3 1 4 to 47 1 2 82 5 mm to 1 207 mm 3 Chrome or Brass with A dimensions 3 to 47 76 2 mm to 1 194 mm Footnotes 1 Part nu...

Page 4: ...Fusible Link Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers Designed for use in Light a...

Page 5: ...5 mm shorter than the A Dimension To locate the deflector at the maximum distance from the wall with no adjustment available order the standard dry horizontal sidewall sprinikler 1 25 mm longer than t...

Page 6: ...1 16 27 mm 5 Escutcheon outer diameter 3 1 16 78 mm 6 Top of deflector to centerline 5 8 16 mm Determining the A Dimension Adustable Recessed HSW Sprinkler with Model E 1 Escutcheon 1 Determine the d...

Page 7: ...to deflector distance 2 1 4 57 mm 4 Top of deflector to centerline 5 8 16 mm 5 Pipe outside diameter Same as 1 13 mm Schedule 40 pipe 1 5 16 33 mm Determining the A Dimension Plain Barrel Dry HSW Spri...

Page 8: ...eaded tee fitting per ANSI 16 4 Class 125 only Exposed Barrel Outer surface of wall Ambient Temperature of the Protected Area at the Discharge End of the Sprinkler Exposed Barrel Ambient Temperature 4...