QUICK RESPONSE
ORDINARY HAZARD DRY
HSW FUSIBLE LINK
SPRINKLERS (8.0K)
(VK2843, VK2883, & VK2923)
TECHNICAL DATA
Page 3 of 8
Form No. F_022717 18.11.01 Rev 18.1.P65
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Approval Chart
Quick Response Ordinary Hazard Dry
HSW Fusible Link Sprinklers (8.0K)
Maximum 175 PSI (12 bar) WWP
Sprinkler
Base Part
Number
1
SIN
Style
Thread Size
Nominal
K-Factor
2
Order Length
Increment
Listings and Approvals
4
(Refer also to Design Criteria on page 4.)
NPT
BSP
Inches mm cULus
5
FM NYC
6
VdS LPCB
21491U
VK2883 Adjustable
Standard
1”
--
8.0 U.S.
(115.2 metric
3
)
1/2”
12.7
A1
--
A1
--
--
--
--
21492U
VK2883
--
25 mm
1/2”
12.7
A1
--
A1
--
--
--
--
21485U
VK2923 Adjustable
Recessed
1”
--
1/4”
6.35
B2
--
B2
--
--
--
--
21486U
VK2923
--
25 mm
1/4”
6.35
B2
--
B2
--
--
--
--
21497U
VK2843
Plain Barrel
1”
--
1/2”
12.7
A3
--
A3
--
--
--
--
21498U
VK2843
--
25 mm
1/2”
12.7
A3
--
A3
--
--
--
--
Approved Temperature Ratings
A - 165 °F (74 °C), 205 °F (96 °C), and 280 °F (138
°C)
B - 165 °F (74 °C) and 205 °F (96 °C)
Approved Finishes and “A” Dimensions
1 - Chrome or White Polyester sprinkler with a Chrome or White Polyester Sleeve and Escutcheon
with “A” dimensions 1-1/2” to 45-1/2” (38.1 mm to 1,156 mm)
2 - Chrome or White Polyester with “A” dimensions 3-1/4” to 47-1/2” (82.5 mm to 1,207 mm)
3 - Chrome or Brass with “A” dimensions 3” to 47” (76.2 mm to 1,194 mm)
Footnotes
1
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2
K-Factor applies for standard lengths (“A” Dimensions indicated above).
3
Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
4
This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any
additional approvals.
5
Listed by Underwriter’s Laboratories for use in the U.S. and Canada.
6
Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. 37.
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating
1
Maximum Ambient
Ceiling Temperature
2
Frame Paint
Color
2
Ordinary
165 °F (74 °C)
100 °F (38 °C)
None
Intermediate
205 °F (96 °C)
150 °F (65 °C)
White
High
280 °F (138 °C)
225 °F (107 °C)
Blue
Sprinkler Finishes:
Brass, Chrome, and White Polyester
Footnotes
1
The sprinkler temperature rating is stamped on the deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.