MODEL V-SD
SPECIFIC APPLICATION
ATTIC SPRINKLER
TECHNICAL DATA
Page 2 of 12
Form No. F_043015 20.07.28 Rev 20.2
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Available Finishes And Temperature Ratings:
Refer to the approval chart on page 3.
Accessories:
(Also refer to the “Sprinkler Accessories” section of the Viking website under Technical Data)
Sprinkler Wrench:
Standard Wrench: Part No. 10896W/B
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A
B. Twelve-head capacity: Part No. 01725A
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During a fire condition, the heat sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap
and sealing spring assembly. Water flowing through the sprinkler orifice strikes the deflector, forming a uniform spray pattern to
extinguish or control the fire, and protect the piping in the interstitial space.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking V-SD Specific Application Sprinkler is available through a network of domestic and international distributors. See The
Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating
1
Maximum Ambient
Ceiling Temperature
2
Bulb Color
Intermediate
200 °F (93.3 °C)
150 °F (65°C)
Green
Sprinkler Finishes:
Brass, ENT
3
1
The sprinkler temperature rating is stamped on the deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3
cULus Listed as corrosion resistant.