MODEL V-SD
SPECIFIC APPLICATION
ATTIC SPRINKLER
TECHNICAL DATA
Page 7 of 12
Form No. F_043015 20.07.28 Rev 20.2
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Figure 4:
Allowed V-SD Attic Sprinkler Under Asymmetrical Slopes
8” (203 mm)
Minimum
Draft curtain or full
wall to deck.
X
X ≠ Y
Y
Refer to Figure 4. V-SD Sprinklers are permitted when the slope
angles are not equal to each other. In this situation, install the
appropriate sprinklers for each respective slope as shown at right.
Vertical riser
Vertical riser
Vertical sprig
Branchline
Armover sprig
X = 6” (150 mm) MAXIMUM
Y= 12” (300 mm) MAXIMUM
Direct mount
Armover
Branchline
X
X
Y
Y
Figure 5:
Exposed CPVC with V-SD Sprinklers