2.5 Test result instructions
Normal
VRLA/ GEL/ AGM/ SLA
STANDARD LSI
Battery voltage: 12.85 V
Fully charged
Fully charged
100% 12.78 V
100% 12.60 V
75% 12.54V
75% 12.42V
50% 12.30V
50% 12.24V
25% 12.12V
25% 12.06V
Total discharge 11.94 V
Total discharge 11.88 V
CCA value 588 CCA
Determine the condition of the battery.
In 24 V test mode, the CCA value refers to the 1/2 value of a
set of two 12 V batteries connected in series.
Internal resistance 4.75 mΩ
The higher the CCA value, the lower the internal resistance
usually is.
Note:
Different material of batteries produced by different
manufacturers can lead to different internal resistances. There
is no fixed standard. But there is little difference between the
internal resistance of batteries with the same model from the
same manufacturer.
In 24 V test mode, the internal resistance value refers to the
total value of a set of two 12 V batteries connected in series.
Service life: indicates the condition of the battery. Plan on
replacing the battery if it shows less than 45%.
Life
Test result
Battery condition
> 80 %
good
Very good
> 60 %
OK
Good
> 45 %
Pay attention
Pay attention, almost no
longer usable
< 45 %
Replace
Cannot be used, must be
replaced
Replacement suggested
The result indicates
that the battery is
poor and has 32% of
its life remaining. It is
suggested that the
battery be replaced.
Service life test OK,
and voltage test low
The result indicates that
the battery is good
and has 100% of its life
remaining. But only
12.11 V remaining. It
is suggested that the
battery be charged.
See image at right.
Service life test OK, and
voltage test too low
The result indicates that
the battery only has 11.88
V remaining and has too
low a voltage, which
can affect the result. At
this point, it is better to
charge before retesting.