Document: LT0554
Vigilant BOWS Installation & Operation Manual
Issue 1.20
6 September 2012
Page 4-1
Before commencing installation, please ensure that the following items
are present and undamaged:
1 x BOWS Unit (50W or 100W)
1 x Installation & Operation Instructions (LT0554
– this document)
1 x Factory Checklist (LT0555)
1 x 003 lock key
1 x LM0359 Battery lead
4 x M5 screws, nuts and washers for attaching battery leads to
batteries
6 x SU0020 cable ties, for general wiring fastening requirements
6 x HW0302 cable tie holders
End-of-Line devices (ELD) as follows:
1 x 3k3 resistor ELD for MX4428 & F3200 Ancil Relays
2 x 10k resistor ALM- Input ELD resistor, MX4428 Ancil Relay ELD
1 x 56k resistor 100V line ELD
2 x 100k resistor 2 branch 100V line ELD
The BOWS cabinet is typically fixed to a wall with four 6 mm screws or
bolts (not included). The drilling details are shown in Figure 13.
The following conditions are required:
1. Dry Area, moderate ambient temperature, 45°C maximum.
2. Not exposed to direct sunlight.
3. Not subject to outdoor conditions without suitable protection.
4. The display should be at average eye level and must not be higher
than 1850 mm or lower than 750 mm above floor level (see Figure
13).
5. Clear access and viewing for operators.
6. At least 1 metre free space should be provided in front of the panel
for installation and maintenance.
7. Must not be installed in hazardous areas as defined in AS3000.
8. If recessed into a wall allow room for the door to open at least
145deg.
It should not be necessary to drill within the cabinet, but if drilling or filing
is required, remove the circuit boards first.
Clean
out all swarf before replacing the boards.
Chapter 4
Installation & Wiring
Checking the
Kit
Mounting