Document: LT0554
Vigilant BOWS Installation & Operation Manual
Issue 1.20
6 September 2012
Page 4-9
The BOWS can be wired to a fire alarm system using separate alarm and
fault wiring. Figure 20 shows examples using VIGILANT fire alarm
panels.
Figure 20. Separate Alarm/Fault Wiring
VIGILANT Fire Alarm Panel Wiring
Separate
Alarm & Fault
Wiring
FLT
0
V
ANCIL
Relay
(
See
Note
4
)
ALM
-
0
V
FLT 0V
FLT
NC
SUP
NO
C
MX
1
10
K
Open
Collector
Output
IOR
F
3200
etc
Input IOR
ADR
ADM
13
X
etc
EOLR
10
K
ALM
-
0
V
Relay Output
F
3200
Relay Bd
,
IOR
,
ADC
130
EOLR
10
K
FLT
FLT
0
V
0
V
FP
1600
MK
3
Sigma
5
Omega
64 MK3
(
See
Note
3
)
E
.
g
.
,
PA
0729
GP Relay Board
ALM
-
0
V
12
V
RELAY
FLT
10
K
FLT
0
V
ALM
-
BELLS
C
/+
BELLS
-
Notes
1.
EOLR value depends upon the fire alarm system‟s input type.
(Not fitted when used with MX1 or 4100ES).
2. Switch SW4 ON on the master T-GEN.
3. FP1600/Omega 64 MK3 boards have three 7-segment displays.
4. Please refer to MX1 LT0360 Installation Manual (NZ) or
LT0439 Operator Manual (Australia) for more information.
COM
0V
ALM-
FLT
EOLR
(see Note 1)
FLT 0V
BOWS
0V
NO
Fault
ALM-
(see note 2)