Vitoligno 300-C Installation/Service
5790 980 - 04
86
Coding
Coding 1
(continued)
Coding in the factory set condition
Possible change
Heating
(continued)
Room sensor room hook-up
B0:0
Is available if code “A0:1” or
“A0:2”, heating group, is set.
Heating mode/reduced mode:
Weather-compensated mode
without room temperature
hook-up
B0:1
Heating mode: Weather-compensated
mode without room temperature
hook-up
Reduced mode: Weather-compensated
mode with room temperature hook-up
B0:2
Heating mode: Weather-compensated
mode with room temperature hook-up
Reduced mode: Weather-compensated
mode without room temperature
hook-up
B0:3
Heating mode/reduced mode:
Weather-compensated mode with
room temperature hook-up
Room sensor room influence factor
B2:0
No room influence factor
B2:1
to
B2:31
Room influence factor adjustable
from 1 to 31
Room sensor summer eco function
B5:0
Without room temperature-
dependent heating circuit
pump logic function
B5:1
to
B5:8
Is available if code “A0:1” or “A0:2”,
heating group, is set.
With room temperature-dependent
heating circuit pump logic function
(see the following table)
Parameter address “B5”: Heating circuit pump “Off”
Summer eco function active
Heating circuit pump “Off”
Summer eco function passive
1
RTactual > RTset + 5 K
RTactual < RTset + 4 K
2
RTactual > RTset + 4 K
RTactual < RTset + 3 K
3
RTactual > RTset + 3 K
RTactual < RTset + 2 K
4
RTactual > RTset + 2 K
RTactual < RTset + 1 K
5
RTactual > RTset + 1 K
RTactual < RTset
6
RTactual > RTset
RTactual < RTset
−
1 K
7
RTactual > RTset
−
1 K
RTactual < RTset
−
2 K
8
RTactual > RTset
−
2
RTactual < RTset
−
3 K
Supply temperature minimum limit
C5:20
Minimum supply temperature
limit set to 68°F (20°C)
C5:10
to
C5:100
Adjustable from 34°F to 212°F
(1°C to 100°C)