Vitoligno 300-C Installation/Service
5790 980 - 04
64
Commissioning, Inspection and Maintenance
Selecting the Pellet Store Sensor
To specify whether a level sensor is present in the pellet
store, press the following keys:
1.
|
/
~
for pellet store sensor “Yes/No”
Selecting the external digital input (external demand)
To specify whether the digital input (junction box
terminal
sm
Ö
) is connected to start/stop the boiler
1.
|
/
~
for pellet store sensor “Yes/No”
2.
d
to confirm.
Setting the Number of Buffer Tank Temperature Sensors
Press the following keys:
1.
|
/
~
for buffer tank temperature sensor “No”,
“3” or “5”
The preset is how many sensors are connected.
Selecting the Type of Heating Water Buffer Tank
If the test point for capturing the system temperature is
to be selected, press the following keys:
1.
|
/
~
for buffer tank type.
“0” for basic heating water buffer tank
“1” for combi tank
2.
d
to confirm.
Selecting an Additional Boiler
If an additional heat generator is to be selected, press
the following keys:
1.
|
/
~
for additional boiler “Yes/No”
2.
d
to confirm.
Control Unit Controls and Display Elements
The programming unit
You can adjust all control unit settings centrally at the
programming unit.
Takes you to the previous step in the menu or
cancels a setting that has been started.
Cursor keys
Scrolls through the menu or adjusts values.
d
To confirm your selection or save the setting
you’ve
made.
?
Calls up the help text relevant to the selected
menu
point.
Calls up the extended menu.
To access the service menu press OK and
simultaneously for approximately 4 sec.