Coding
Coding 1
(continued)
Coding in the factory set condition
Possible change
Additional heat generator
Is available if code “Additional boiler: Yes”, hardware group, is set.
Buffer tank charging until sensor
D0:1
The additional heat generator
charges the heating water
buffer tank up to the first
buffer tank temperature
sensor.
Note:
Only useful if the
additional heat generator has
its own boiler circuit pump.
D0:0
The heating water buffer tank
temperatures are ignored.
D0:2
The additional heat generator charges
the heating water buffer tank up to the
second buffer tank temperature sensor.
D0:3
The additional heat generator charges
the heating water buffer tank up to the
third buffer tank temperature sensor.
D0:4
The additional heat generator charges
the heating water buffer tank up to the
fourth buffer tank temperature sensor.
D0:5
The additional heat generator charges
the heating water buffer tank up to the
fifth buffer tank temperature sensor.
Buffer tank charging until temperature
D1:75
The additional heat generator
charges the heating water
buffer tank until the
temperature of 167°F (75°C)
at the selected sensor
(code “D0:1-5”) is reached.
D1:50
to
D1:100
Adjustable value in °C
Start delay
D2:10
Start delay of the additional
heat generator of 10 min
D2:0
to
D2:250
Adjustable value in min
Start temperature set system temperature
D3:-10
Start temperature of the
additional heat generator.
Starting condition:
Actual system temperature
< set system temperature
minus value set (here: 10 K)
D3:-100
to
D3:-1
Adjustable value in K
Minimum runtime
D4:5
Minimum runtime of the
additional heat generator
of 5 minutes
D4:0
to
D4:250
Adjustable value in min
Min pause duration
D5:5
Minimum pause duration of
the additional heat generator
of 5 minutes
D5:0
to
D5:250
Adjustable value in min
Start without delay, Set system temp
D6:-20
Start of additional heat
generator without delay.
Condition: Actual system
temperature < set system
temperature minus value set
(here: 20 K)
D6:-100
to
D6:0
Adjustable value in K
Parallel operation
D7:1
Parallel operation of both
heat generators is possible.
Note:
Parallel operation only
possible when the additional
heat generator
has a boiler circuit pump.
D7:0
Parallel operation of both boilers is
not possible.