62
5603 878 - 04
Vitoflex 300-RF Installation & Operating
ECOTRONIC Control System
(continued)
Screen number Screen text
Parameter description
Factory setting
(6)
Feed system 1
.........
light barrier
delay
Delay of the conveying equipment 1 light barrier
(e.g. in-feed auger 1)
Only display if:
Conveying equipment 1 available with light barrier
500 ms
(7)
to
(22)
Feed system 2
to conveying
equipment 15
light barrier delay
Delay of the conveying equipment 2 to 15 light barriers
Only display if:
Conveying equipment available with light barriers
500 ms
(30)
Extraction system 1
....
preferred direction
Extraction system 1 with preferred rotating direction
available?
Only display if:
Extraction system with reversing (funnel extraction system)
No
(31)
Extraction system 1
.....
reversing interval
Reversing interval extraction system 1
Preferred direction YES: The extraction is reversed in
the event of an overload (current measurement) for the
duration of the reversing interval. Subsequently preferred
direction of rotation.
Preferred direction NO: Extraction is reversed in the
event of an overload (current measurement) and after the
duration of the reversing interval.
Only display if:
Extraction system with reversing
(funnel extraction system)
240 sec
(33)
Extraction system 1
cross load module
light barrier delay
Delay of the light barrier walking floor auger extraction
system 1
Only display if:
Extraction system 1 hydraulic extraction system available
2500
ms
(34)
Extraction system 1
cross load module
maximum operating
time
Maximum operating time of the walking floor auger
extraction system 1 with walking floor auger light barrier
broken
forced control hydraulic drive
Only display if:
Extraction system 1 hydraulic extraction system available
80 sec
(35)
Extraction system 1
Hydraulics
pulse
Following expiration of the maximum operating time of the
walking floor auger extraction system 1 with broken light
barrier of the walking floor auger, the hydraulic unit is
force-controlled for this pulse time.
Only display if:
Extraction system 1 hydraulic extraction system available
20 sec
(40)
Extraction system 2
......
Preferred direction
Extraction system 2 with preferred rotating direction
available?
Only display if:
Extraction system with reversing (funnel extraction system)
No
5.2 Loading Service Menu
(continued)
Operation