59
5603 878 - 04
Vitoflex 300-RF Installation & Operating
Operation
ECOTRONIC Control System
(continued)
Screen number Screen text
Parameter description
Factory setting
(41)
Ember monitoring system
Switch-off delay
Target
Delay ember bed light barriers until in-feed auger stops
(in-feed auger operating time is monitored)
30 sec
(42)
In-feed auger
Ember monitoring system
Cycle ramp
With a broken ember bed light barrier, the duty cycle
of the in-feed auger is reduced in accordance with this
timing generator
20 sec
(50)
Flue gas blower
Maximum rotational
speed
Maximum speed of the flue gas exhaust blower
70%
(51)
Flue gas blower Minimum
rotational speed
Minimum speed of the flue gas exhaust blower
30%
(52)
Flue gas blower initial
rotational speed
At the start of automatic mode (heat up) the flue gas
blower is regulated at this speed.
50%
(60)
Frequency converter 1
Status display of the frequency converter flue gas blower
(61)
Timer number
Time module display
-
(62)
Controller number
Controller module display
-
(63)
Error number
Error memory:
Display of the last 30 error messages with date and time
(64)
Log for the RS 232
Select the log for the serial interface on the control module
KOB
for trend display/archiving KOB (AnzWIN)
Visualization
for visualization / data archiving
ModBus
in operation
Only display if:
Export operating data via interface option
KOB
(65)
Visualization address
Controller address system visualization
Only display if:
Export operating data via interface option and
log for the RS 232 = Visualization
110
(68)
Oxygen sensor
Oxygen sensor calibration function:
If Vitoflex 300-RF ECO is not in operation, the oxygen
sensor can be recalibrated with this function.
No
(69)
Load basic setting
Reset all Vitoflex 300-RF ECO parameters (Parameters -
Menu and Service - Menu) to factory settings
No
(70)
Language
Selection of the user language
(73)
MMC
Status display for the data logger (for archiving data on
the MMC dongle)
4.2 Service Menu (continued)