60
5603 878 - 04
Vitoflex 300-RF Installation & Operating
ECOTRONIC Control System
(continued)
5.0 Vitoflex 300-RF ECO loading
Green LED - flashes with an active menu
Red LED - illuminates with loading fault
5.1 Loading menu
Menu designation: - Loading
Access menu: - Press F4 briefly
Exit menu: - Press F4 briefly or automatically after 60 seconds
Note:
Depending on the design and setting, some menus and text do not appear.
Screen number Screen text
Parameter description
Factory setting
(1)
Cleaning
Activation of cleaning function (only possible if Vitoflex
300-RF ECO
Off).
During the cleaning function the grate motor is
operated in long-term operation and the flue gas blower
is operated with the automatic starting speed
No
(5)
Grate drive
Pause
In load operation (manual and automatic mode) the
grate drive is controlled with an adjustable idle time.
(Pulse: 2 seconds, pause adjustable)
60 sec
(6)
Dosing container
Idle run time
Operating time of the in-feed auger with free in-feed
auger light barrier
Start conveying equipment
5 sec
(7)
Feed system 1
.......
delay
Switch-on delay of the feed system 1
(e.g. rotary valve, in-feed auger 1,..)
Only display if:
Feed system 1 available
3 sec
(8)
Feed system 1
.....
Post flow
Post flow of the feed system 1
(e.g. conveyor auger)
Only display if:
Feed system 1 available with post flow function
(e.g. conveyor auger)
0 sec
(9)
to
(37)
Feed system 2 - 15
Switch-on delay or post flow of the conveying
equipment 2 to 15
Only display if:
Feed system 2 - 15 available or
Feed system with post flow function available
(38)
Extraction system 1
.....
delay
Switch -on delay of the extraction system 1
(e.g. spring extraction system, pellet extraction auger)
Only display if:
Extraction system 1 available
3 sec
(39)
Extraction system 1
.....
pulse
Pulse of the cycle extraction system 1
(e.g. spring extraction system, pellet extraction auger)
Only display if:
Extraction system 1 available or extraction system 1
available with clock circuit
5 sec
(40)
Extraction system 1
......
Pause
Pause of the cycle extraction system 1
(e.g. spring extraction system, pellet extraction auger)
Only display if:
Extraction system 1 available or extraction system 1
available with clock circuit
0 sec
Operation